Plan Review Details - Permit 00010763
Plan Review Stops For Permit 00010763
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-01 Cont ID  
Sent By dpalmer Date 2000-03-01 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2000-03-01 Time 14:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-21 Cont ID  
Sent By dpalmer Date 2000-01-21 Time 06:20 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE:AS PER OUR CONVERSATION PLEASE
 CHECK FAULT CURRENT CALCULATIONS FOR
 AIC RATING. FPL CAN GIVE FALUT CURRENT
 AVAILABILITY.
  
 2)NOTE:PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO BLDG.STEEL ALSO AS S
 REQ`D BY 250-81 FO THE NEC.
  
 3)NOTE: BATH(S) CIRCUT DOES NOT NEED TO
 BE INCLUDED IN LOAD CALCULATION BUT
 NEEDS TO BE ON PANEL SCHEDULE.
  
 4)NOTE: RISER DIAGRAM SHOWS FEEDTO
 PANEL GOING OVERHEAD. IF THIS IS THE
 CASE THERE CANNOT BE OVER 8`OF CONDUCTOR
 INSIDE THE STRUCTURE AS PER ART;230-70A
 OF THE NEC. IF IT IS GOING TO BE IN-
 -STALLED IN SLAB THEN PLEASE SHOW.
  
 PLESE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS;
 CALL; 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-13 Cont ID  
Sent By cthirben Date 2000-03-13 Time 16:37 Rev Time 0.50
Received By cthirben Date 2000-03-13 Time 16:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-01-24 Cont ID  
Sent By fknapp Date 2000-01-24 Time 16:03 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED PER BILL STAPLES

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-19 Cont ID  
Sent By tlarge Date 2000-01-19 Time 07:49 Rev Time 0.50
Received By tlarge Date 2000-01-19 Time 07:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-24 Cont ID  
Sent By fknapp Date 2000-01-24 Time 14:19 Rev Time 4.00
Received By fknapp Date 2000-01-24 Time 10:28 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 SBC 104.2.2
  
 1)PROVIDE JOB/SITE LOCATION ON PRODUCT
 APPROVAL SUBMITTAL FORMS.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVAL FOR FRONT DOOR ASSEMBLY WITH
 SIDELITE.
  
 3)PROVIDE SAFETY GLASS AS NOTED ON PLAN.
  
 4)PROVIDE NAILING FOR PLYWOOD SHEATHING
 AS NOTED ON PLAN PER CITY AMENDMENTS
 2306.1
  
 5)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS WITH SPECIFIC
 ANCHORS TO BE USED.
  
 PLEASE SUBMIT PRIOR TO INSTALLATION.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-24 Cont ID  
Sent By fknapp Date 2000-01-24 Time 16:03 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED PER GRACE JOYCE