Miscellaneous Information / Notes |
INSTALL 1258SQFT OF VINYL FLOORING |
|
7/24/23 FAILED FIRE CLF |
THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L |
FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
COMMENTS: |
|
1) THERE ARE INDICATIONS OF VINYL FLOORING BUT NO |
SPECIFICATIONS SHEETS THAT INDICATE MEETING THE |
REQUIREMENTS PER NFPA' |
|
PER NFPA 101, CHAPTER 10 SECTION 10.2.7 |
|
10.2.7* INTERIOR FLOOR FINISH TESTING AND |
CLASSIFICATION. |
10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
FINISHES SHALL |
COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
IGNITION |
CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
MATERIALS. |
10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR |
WHICH 10.2.2.2 |
ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, |
SHALL HAVE A |
MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
|
10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED |
IN THE CLASSES SPECIFIED |
IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH |
THE CRITICAL RADIANT FLUX |
REQUIREMENTS. |
10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
INTERIOR FLOOR FINISH |
SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS |
THAN 0.45 W/CM2, AS DETERMINED |
BY THE TEST DESCRIBED IN 10.2.7.3. |
10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS |
II INTERIOR FLOOR FINISH |
SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS |
THAN 0.22 W/CM2, BUT LESS |
THAN 0.45 W/CM2, AS DETERMINED BY THE TEST |
DESCRIBED IN 10.2.7.3. |
|
PLEASE REVIEW AND PROVIDE SPEC SHEETS. |
|
|
|
CAITLIN L FRANCIS |
FIRE INVESTIGATOR |
561-804-4728 |
[email protected] |
|
|
**NEED QUALIFIER'S NOTARIZED SIGNATURE ON APP |
PRIOR TO ISSUANCE - SIGNATURE IS NOT QUALIFIER** |
|
|