Permit Information - Permit 22121242

Loading permit details...

Permit Information
Permit Number 22121242 Property ID 74434304010000760
Permit Desc EVENT Balance Due $0.00
Property Address 6000 N FLAGLER DR Status Revoked

Permit Plan Reviews Inspections Fees Contractors All
Permit
Permit Information
Application Date 2022-12-28 Operator bbennett
Issued Date 2023-01-12 Operator bbennett
Master Number   Project Number  
C.O. Number   Operator  
C.O. Issued  
C-404 Type   Usage Class PRIVATE
Applied Value 0 Units 0
Calculated Value 0 Contractor ID 489 EXEMPT
Property On Permit
Property ID 74434304010000760    
Building Ext. 0001
Address 6000 N FLAGLER DR
City WEST PALM BEACH
State FL
Zip Code 33407
Owner On Permit
Name FLORIDA POWER & LIGHT CO
Address 700 UNIVERSE BLVD
City JUNO BEACH Type  
State FL Zip Code 33408 2683
Miscellaneous Information / Notes
MANATEE FEST 7TH ANIVERSARY
FEB 4TH 2023 FROM 9AM TO 4PM
 
12/28/22 PASS FIRE CLF
THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
COMMENTS:
PLEASE CONSIDER THE FOLLOWING AS PROVISO:
 
THESE PROVISO COMMENTS WILL BE VERIFIED AND
CONFIRMED AT THE TIME OF FIRE INSPECTION. FAILURE
TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN A
FAILED FIRE INSPECTION.
 
GENERATORS AND OTHER INTERNAL COMBUSTION POWER
SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM
OF 5 FEET AND SHALL BE PROTECTED FROM CONTACT BY
FENCING OR ENCLOSURE.
 
PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL
BE TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED
75 FEET. PROVIDE TYPE K EXTINGUISHERS WHEN COOKING
WITH GREASE OR WHEN PRODUCING SMOKE OR
GREASE-LADEN VAPORS.
 
TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
BUILDING STRUCTURES.
 
TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT
SIGNS ARE REQUIRED FOR TENTS EXCEEDING 1,200
SQUARE FEET.
 
POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
LOCATIONS.
 
PROVIDE NON-COMBUSTIBLE CANOPY MATERIAL.
PER FL STATUTE 633.202
 
A TENT UP TO 900 SQUARE FEET IS EXEMPT FROM THE
FLORIDA FIRE PREVENTION CODE, INCLUDING THE
NATIONAL CODES INCORPORATED BY REFERENCE.
 
CAITLIN L FRANCIS
FIRE INVESTIGATOR
561-804-4728
[email protected]