Miscellaneous Information / Notes |
RENOVATE KITCHEN AND 2 BATHROOMS |
|
|
|
|
8/25/22 PLANS RELEASED, PERMIT CARD UPLOADED AO |
8/9/22 REVIEWS COMPLETE, WAITING ON UPDATED SUB |
CONTRACTOR INFO (ELEC & PLUMB) TO ISSUE PERMIT. |
LEM |
8/4/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
8/3/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
7/26/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
7/26/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
7/20/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
7/19/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
7/11/22, PASS FIRE, CRW |
7/9/22 APPLICANT RESUBMITTED DIGITALLY,INCOMING |
COMPLETE AO |
7/6/22 REVIEWS COMPLETE, APPLICANT INVITED TO |
RESUBMIT. LEM |
5/25/22 RESUBMIT RECEIVED, INCOMING COMPLETE. LEM |
5/23/22 REVIEWS COMPLETE, APPLICANT NEEDS TO |
RESUBMIT. LEM |
4/22/22, FAIL FIRE, CRW, PROVIDE SPECIFIC LOCATION |
REQUIREMENTS FOR SMOKE ALARMS ON THE ELECTRICAL |
PLAN. NFPA 72 29.8.3.4 |
THE ELECTRICAL PLAN HAS A NOTE THAT ALL EXISTING |
FLOORING IS TO BE REMOVED AND REPLACED THROUGHOUT |
THE ENTIRE UNIT. PROVIDE SPECIFICATIONS ON |
FLOORING TO BE INSTALLED FOR FIRE PERFORMANCE |
INCLUDING THE CRITICAL RADIANT FLUX OF THE |
MATERIAL. NFPA 101 10.2.7 |
|
|
|
4/21/22 PLANS UPLOADED,INCOMING COMPLETE.CD |
4/6/22 APPLICANT INVITED TO UPLOAD PLANS AND PAY |
FEES. LEM |