Miscellaneous Information / Notes |
REPLACE EXISTING FIRE ALARM PANEL WITH FLMS5UD |
|
4/14/2023 PERMIT CLOSED PP |
01/16/19 BRIAN PICKED UP PERMIT BB |
1/15/19 MOVED PLANS TO LARGE "T". AM |
1/15/19 PLAN REVIEW COMPLETE, CUSTOMER INFORMED, |
READY TO BE PICKED UP, FILED UNDER SMALL "T". CP |
1/10/19 SCOTT RESUB TO ADDRESS DENIED COMMENTS. AM |
6/11/18 PLAN REVIEW COMPLETE, CUSTOMER INFORMED |
THEY NEED TO RESUBMIT, FILED UNDER SMALL DENIED |
"T". CP |
6/5/18 - FIRE PASSED WITH THE FOLLOWING PROVISO: |
|
1. PROVIDE COMPATIBILITY REPORT AT TIME OF |
INSPECTION OF EXISTING DEVICES WITH NEW FACP. |
|
2. ENSURE THAT NOTIFICATION APPLIANCES ARE |
CREATING 75DB AT THE PILLOW TOP OF EACH BEDROOM IN |
ACCORDANCE WITH NFPA 72 ? 7.4.4.1 |
|
3. TEST ALL EXISTING DEVICES TO ENSURE |
COMPATIBILITY AND FUNCTIONALITY WITH NEW FACP. |
|
4. PROVIDE RECORD OF COMPLETION AT TIME OF |
INSPECTION. |
|
5. NOTIFY OWNERS AND ALL TENANTS 24 HOURS IN |
ADVANCE OF FIRE ALARM TESTING WITH THE AHJ. |
NOTIFICATION SHALL BE PROVIDED BY POSTING EACH |
UNIT. |
|
6. PROVIDE NFPA CODE COMPLIANT ?LOCAL ALARM ONLY? |
SIGNAGE AT EACH PULL STATION. |
|
7. ANY DETECTORS EXPOSED TO THE ELEMENTS OR |
INSTALLED INSIDE OF AN AIR CONDITIONED OR FAN |
CONDITIONED FACP SURFACE MOUNTED ENCLOSURE SHALL |
BE HEAT DETECTION AS OPPOSE TO SMOKE DETECTION TO |
ALLEVIATE FALSE ALARMS. |
|