Permit Information - Permit 18051355

Loading permit details...

Permit Information
Permit Number 18051355 Property ID 74424312030010120
Permit Desc FA Balance Due $0.00
Property Address 1441 BRANDYWINE RD BLDG 800 Status Closed

Permit Plan Reviews Inspections Fees Contractors All
Permit
Permit Information
Application Date 2018-05-29 Operator bbennett
Issued Date 2019-01-16 Operator bbennett
Master Number   Project Number  
C.O. Number   Operator  
C.O. Issued  
C-404 Type   Usage Class PRIVATE
Applied Value 2488 Units 0
Calculated Value 0 Contractor ID FL01051
Property On Permit
Property ID 74424312030010120    
Building Ext. 0008
Address 1441 BRANDYWINE RD BLDG 800
City WEST PALM BEACH
State FL
Zip Code 33409
Owner On Permit
Name NORTHLAND WINDWARD LLC
Address 20410 CENTURY BLVD # 145
City GERMANTOWN Type Private
State MD Zip Code 20874 1181
Miscellaneous Information / Notes
REPLACE EXISTING FIRE ALARM PANEL WITH FLMS5UD
 
4/14/2023 PERMIT CLOSED PP
01/16/19 BRIAN PICKED UP PERMIT BB
1/15/19 MOVED PLANS TO LARGE "T". AM
1/15/19 PLAN REVIEW COMPLETE, CUSTOMER INFORMED,
READY TO BE PICKED UP, FILED UNDER SMALL "T". CP
1/10/19 SCOTT RESUB TO ADDRESS DENIED COMMENTS. AM
6/11/18 PLAN REVIEW COMPLETE, CUSTOMER INFORMED
THEY NEED TO RESUBMIT, FILED UNDER SMALL DENIED
"T". CP
6/5/18 - FIRE PASSED WITH THE FOLLOWING PROVISO:
 
1. PROVIDE COMPATIBILITY REPORT AT TIME OF
INSPECTION OF EXISTING DEVICES WITH NEW FACP.
 
2. ENSURE THAT NOTIFICATION APPLIANCES ARE
CREATING 75DB AT THE PILLOW TOP OF EACH BEDROOM IN
ACCORDANCE WITH NFPA 72 ? 7.4.4.1
 
3. TEST ALL EXISTING DEVICES TO ENSURE
COMPATIBILITY AND FUNCTIONALITY WITH NEW FACP.
 
4. PROVIDE RECORD OF COMPLETION AT TIME OF
INSPECTION.
 
5. NOTIFY OWNERS AND ALL TENANTS 24 HOURS IN
ADVANCE OF FIRE ALARM TESTING WITH THE AHJ.
NOTIFICATION SHALL BE PROVIDED BY POSTING EACH
UNIT.
 
6. PROVIDE NFPA CODE COMPLIANT ?LOCAL ALARM ONLY?
SIGNAGE AT EACH PULL STATION.
 
7. ANY DETECTORS EXPOSED TO THE ELEMENTS OR
INSTALLED INSIDE OF AN AIR CONDITIONED OR FAN
CONDITIONED FACP SURFACE MOUNTED ENCLOSURE SHALL
BE HEAT DETECTION AS OPPOSE TO SMOKE DETECTION TO
ALLEVIATE FALSE ALARMS.
 