Miscellaneous Information / Notes |
PERMITTING FOR INTERIOR IMPROVEMENTS,*CHANGE OF |
OCCUPANCY FROM S2 TO BUSINESS* |
|
|
5/16/16 PERMI P/U BY JOSEPH MS |
|
5/5/16 CONTRACTOR APPLICATION SUBMITTED ASM |
3/8/16- READY IN LARGE C/EMAILED CONTACT PERSON/CC |
3-2-16 OK PER S HILL TO ROUTE "SUBMITTAL" OF |
REVISED ENERGY CALCULATIONS" TO HER DESK WL |
2/29/16 ON SH DESK PENDING RECEIPT OF INFORMATION |
FROM ARCHITECT |
1/27/16 PASSED BY FIRE WITH PROVISO COMMENTS, |
RETURNED TO B26.PML |
1/19/16 RESUB ADDRESSING DENIED COMMMENTS MS |
|
12/7/15 PLAN REVIEW COMPLETE, CUSTOMER NEEDS TO |
RESUBMIT, FILED UNDER LARGE DENIED "TBD". CP |
11/23/15 ON MARIO'S DESK. CP |
11/20/15 - FAILED BY FIRE. RETURNED TO B3 |
1. PROVIDE RAILING DETAIL FOR MEZZANINE |
2. PROVIDE DOOR RATINGS FOR DOORS 04, 05, 06 |
3. PROVIDE STAIR DETAIL |
4. PROVIDE RATING OF WAREHOUSE WALL THAT PROVIDES |
SEPARATION TO THE OFFICE SPACE |
5. PROVIDE RATING OF STORAGE ROOM WALL THAT |
PROVIDES SEPERATION FROM THE OFFICE SPACE |
6. REVIEW / REVISE FIRST FLOOR EGRESS PLAN (CAN |
NOT EGRESS FROM LOWER HAZARD THROUGH HIGHER HAZARD |
7. STORAGE SHOW UNDER STAIR. PROVIDE DETAIL OF |
PROTECTION (SPRINKLER, ETC..) |
8. SPRINKLER MODIFICATIONS MAY BE NEEDED. HAVE |
EVALUATED. IF NEEDED SUBMIT UNDER SEPERATE PERMIT. |
9. FIRE ALARM MODIFICATIONS MAY BE NEEDED TO MEET |
NOTIFICATION REQUIREMENTS, HAVE EVALUATED. IF |
NEEDED SUBMIT UNDER SEPERATE PERMIT. GJT |
|
|
|
|
|
11/18/15 REVISED PERMIT APPLICATION DESCRIPTTION |
(CHANGE OF OCCUPANCY REQUIRED) SH |
11/9/15 ROUTED TO SKENNEDY SEW |