INSPECTION DETAILS FOR PERMIT 16100451 |
Permit Number |
16100451 |
Owner Name |
LENNAR HOMES INC |
Permit Type |
ELEC-SUB |
Permit Address |
5200 ASHLEY RIVER RD |
Inspection Type |
ELECTRICAL FINAL-5 |
City |
WEST PALM BEACH |
Inspect Area |
|
Inspector |
0022-E |
Request Date |
2017-02-27 |
Scheduled Date |
2017-02-28 |
Instructions |
|
Contract Info |
|
Contractor |
|
Inspect Date |
2017-02-28 |
Result |
F |
Fail Code |
|
Comments |
|
Work Time |
|
Confirm |
461927 |
Fee ID |
|
|
Inspector Notes |
Date |
Text |
2017-02-28 15:38:32 | PLASTIC BUSHING REQUIRED ON WIRE #4 AND | | LARGER 300,4(G) LFMC SHALL NOT BE USED | | WHERE SUBJECT TO PHYSICAL DAMAGE 350.12. |
|