Plan Review Notes For Project Z23060038
Project Number Z23060038
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-07-07 15:51:13FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 1) SUBMITTED PLANS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 303
  
 1.1.1 THIS STANDARD ALSO APPLIES TO SUPPORT FACILITIES
 AND STRUCTURES USED FOR CONSTRUCTION, REPAIR, STORAGE,
 HAULING AND
 LAUNCHING, OR FUELING OF VESSELS IF FIRE ON A PIER
 WOULD POSE AN IMMEDIATE THREAT TO THESE FACILITIES, OR
 IF A FIRE AT A REFERENCED
 FACILITY WOULD POSE AN IMMEDIATE THREAT TO A DOCKING
 FACILITY.
  
 1.1.2 THIS STANDARD APPLIES TO MARINAS AND FACILITIES
 SERVICING
 SMALL RECREATIONAL AND COMMERCIAL CRAFT, YACHTS, AND
 OTHER
 CRAFT OF NOT MORE THAN 300 GROSS TONS.
  
  
 2) THE FIRE DEPARTMENT SHALL BE PROVIDED WITH ACCESS TO
 THE PROPOSED.
  
 PER NFPA 303
 4.2.2 FIRE DEPARTMENT ACCESS.
 4.2.2.1 THE FIRE DEPARTMENT SHALL HAVE ACCESS TO
 FENCED, GATED, OR LOCKED GROUNDS OR PIERS.
 4.2.2.2 APPROPRIATE MEANS OF ACCESS SUCH AS KEYS,
 CARDKEYS, OR COMBINATIONS SHALL BE
 PROVIDED TO THE FIRE DEPARTMENT OR SHALL BE PERMITTED
 TO BE SECURED IN A LOCK BOX ON THE
 PREMISES ACCESSIBLE TO THE FIRE DEPARTMENT
  
  
 3) FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA
 6.2 PORTABLE FIRE EXTINGUISHERS.
 6.2.1 PLACEMENT.
 6.2.1.1 PLACEMENT OF PORTABLE FIRE EXTINGUISHERS SHALL
 BE IN ACCORDANCE WITH CHAPTER 5 OF
 NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS,
 UNLESS OTHERWISE PERMITTED BY 6.2.1.1.1, 6.2.1.1.2,
 OR 6.2.1.1.3
 6.2.1.1.1 PLACEMENT OF PORTABLE FIRE EXTINGUISHERS ON
 PIERS
 AND ALONG BULKHEADS WHERE VESSELS ARE MOORED OR ARE
 PERMIT TED TO BE MOORED SHALL MEET THE FOLLOWING
 CRITERIA:
 (1) EXTINGUISHERS LISTED FOR CLASS A, CLASS B, AND
 CLASS C FIRES
 SHALL BE INSTALLED AT THE PIER/LAND INTERSECTION ON A
 PIER
 THAT EXCEEDS 25 FT (7.62 M) IN LENGTH.
 (2) ADDITIONAL FIRE EXTINGUISHERS SHALL BE PLACED SUCH
 THAT THE
 MAXIMUM TRAVEL DISTANCE TO AN EXTINGUISHER DOES NOT
 EXCEED 75 FT (22.86 M)
  
  
 4) A STANDPIPE SYSTEM IS REQUIRED PER NFPA 303
 6.4* FIRE STANDPIPE SYSTEMS.
 6.4.1 CLASS I STANDPIPE SYSTEMS SHALL BE PROVIDED FOR
 PIERS, BULKHEADS, AND BUILDINGS WHERE THE HOSE LAY
 DISTANCE FROM THE
 FIRE APPARATUS EXCEEDS 150 FT (45 M).
  
 5) A FIRE HYDRANT COULD NOT BE IDENTIFIED AND IF
 APPLICABLE SHALL BE REQUIRED.
  
 A HYDRANT WOULD BE REQUIRED FOR THE FDC STANDPIPE
 SYSTEM AND BE WITHIN 100' OF EACH OTHER PER NFPA 14
 6.6 HYDRANTS AND WATER SUPPLIES. HYDRANTS AND WATER
 SUPPLIES FOR FIRE PROTECTION IN MARINAS AND BOATYARDS
 SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 13, STANDARD FOR THE INSTALLATION
 OF SPRINKLER SYSTEMS; NFPA 14, STANDARD FOR THE
 INSTALLATION OF STANDPIPE AND HOSE
 SYSTEMS; AND NFPA 24, STANDARD FOR THE INSTALLATION OF
 PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES
  
 6) ANY ELECTRICAL WORK OR ELECTRICAL SERVICE SHALL
 COMPLY WITH THE REQUIREMENT OF NFPA 70 AND NFPA 303
  
 5.1 NATIONAL ELECTRICAL CODE. THE REQUIREMENTS SET
 FORTH HEREIN SUPPLEMENT AND RELATE THE REQUIREMENTS OF
 NFPA 70,
 NATIONAL ELECTRICAL CODE, TO THE SPECIFIC CONDITIONS
 AND COMBINATIONS OF CONDITIONS FOUND IN MARINAS AND
 BOATYARDS AND SHALL
 BE FOLLOWED IN ADDITION TO ANY REQUIREMENTS FOUND IN
 NFPA 70, INCLUDING, BUT NOT LIMITED TO, ARTICLE 555.
  
 5.2 LISTED OR LABELED. ALL ELECTRICAL MATERIALS,
 DEVICES, APPLIANCES, FITTINGS, AND OTHER EQUIPMENT
 SHALL BE LISTED OR LABELED
 BY A QUALIFIED TESTING AGENCY AND SHALL BE INSTALLED
 AND CONNECTED IN ACCORDANCE WITH LISTING REQUIREMENTS
 AND/OR MANUFACTURERS INSTRUCTIONS.
  
 5.3 ELECTRICAL DATUM PLANE.
  
 5.3.1 A BENCH MARK INDICATING THE ELECTRICAL DATUM
 PLANE (SEE3.3.7) OF THE LAND AREA SHALL BE PERMANENTLY
 LOCATED ON SHORE
 IN THE MARINA OR BOATYARD.
  
 5.3.2 ELECTRICAL SERVICES SHALL BE DISCONNECTED FROM
 THE POWER SOURCE WHEN THE WATER LEVEL REACHES THE BENCH
 MARK FOR THE
 ELECTRICAL DATUM PLANE.
  
 5.3.3 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT
 LEAST 12 IN. (305 MM) ABOVE THE DECK OF A FLOATING
 PIER.
 5.3.4 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT
 LEAST 12 IN. (305 MM) ABOVE THE DECK OF A FIXED PIER
 BUT NOT BELOW THE
 ELECTRICAL DATUM PLANE. (SEE 5.12.1 FOR RECEPTACLE
 LOCATIONS.)
  
 5.9 ELECTRICAL INSTALLATION.
  
 5.9.1 WIRING ELECTRICAL EQUIPMENT AND MATERIALS
 INSTALLED ON PIERS, WHARVES, DOCKS, OR SIMILAR
 LOCATIONS, AND WIRING METHODS
 SHALL SPECIFICALLY CONFORM TO THE REQUIREMENTS OF
 ARTICLE 555 AND ANY OTHER APPLICABLE REQUIREMENTS OF
 NFPA 70, NATIONAL
 ELECTRICAL CODE.
  
 7) FIRE SHALL REVIEW ALL SUBMITTED PROJECT PLANS AT THE
 APPLICABLE TIME AND IN ACCORDANCE WITH THE REQUIREMENTS
 OF ALL APPLICABLE FIRE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  