2023-07-13 11:31:59PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -BACKFLOW ASSEMBLY CALLED OUT FOR RELOCATION MUST BE
 REPLACED AS IT IS NOT LEAD FREE COMPLIANT. ALSO
 INDICATE RP TYPE, LEAD FREE, AND SIZE.
 -EXISTING METER AT WESTERN METER BOX IS 1 INCH SIZE.
 ACCOUNT HOLDER IS PALM BEACH COUNTY AND ADDRESS 901
 EVERNIA ST. #I IN UTILITY BILLING SYSTEM.
 -THERE IS NO EXISTING METER IN THE EASTERN METER BOX.
 -EASTERN BACKFLOW ASSEMBLY NEEDS TO BE LABELED AS RP
 TYPE AND LEAD FREE. PIPING UPSTREAM BACKFLOW ASSEMBLY
 CANNOT BE PVC. ALSO OLD PIPING MAY NEED TO BE REMOVED
 AND REPLACED UNDER SIDEWALK.
 RESPECTFULLY,
 MARK HURLEY [email protected]