Plan Review Notes
Plan Review Notes For Project Z23060031
Project Number Z23060031
Review Stop PU
Sequence Number 1
Notes
Date Text
2023-07-13 11:56:10-MANHOLE WILL REQUIRE REHABBING
 -LATERLAS LARGER THAN 6" WILL REQUIRE CONNECTION TO A
 MANHOLE WITH A CLEANOUT OF CORRESPONDING SIZE ALONG THE
 R/W
 -UTILITY CROSSING INFO MISSING
 -SHOW ALL LATERALS/SERVICES ALONGSIDE PROJECT LIMITS.
 -PREFERENCE WOULD BE TO AVOID TAPPING THE 20" MAIN FOR
 THE HYDRANT
 -PROVIDE DIMENSIONS BETWEEN TAPS AND ADHERE TO GN
 SECTION OF STANDARD DETAILS FOR HORIZONTAL AND VERTICAL
 SEPARATION
 -CCTV OF GRAVITY MAIN REQUIRED BOTH PRIOR AND AFTER
 CONSTRUCTION
 -DENOTE BACKFLOW TYPES BY USE
 -PROVIDE DEMAND CALCS AND LOS TO DETERMINE SUFFICIENT
 FLOW FROM EXISTING PIPE
 -SHOW ALL EXISTING VALVES AND APPURTENENCES
 -5 FOOT RADIAL CLEARANCE REQUIRED FOR METER BOXES AND
 CLEANOUTS
 -PROVIDE PROFILES FOR ALL CONNECTIONS FROM POINT OF
 CONNECTION TO POINT OF SERVICE
 -DENOTE THE DOWNSTREAM LIFT STATION THAT THE PROJECT
 AREA SERVES
 -EXISTING LATERALS/SERVICES NOT TO BE USED MUST BE
 REMOVED AND CAPPED AT THE MAIN
  