| Plan Review Notes For Project Z23060022 |
| Project Number |
Z23060022 |
|
| Review Stop |
PU-CS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-06 11:46:56 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -JUSTIFICATION STATEMENT SAYS THAT THE PROPERTY IS ON | | | THE NORTH SIDE OF ALPHA ST., BUT PLANS SEEM TO SHOW IT | | | ON THE SOUTH SIDE. | | | -1.5 INCH WATER METER HAS 2 INCH WATER SERVICE PIPING | | | BETWEEN MAIN AND METER PER STANDARD DETAILS AND AML. | | | -SPECIFICALLY ADD SIZE OF BACKFLOW ASSEMBLY ON THE | | | LABEL. | | | -VERIFY IF THE NEW BUILDING WILL HAVE FIRE SPRINKLERS. | | | IF SO, WILL NEED SEPARATE DEDICATED FIRELINE WATER | | | SERVICE WITH DETECTOR BACKFLOW ASSEMBLY. | | | -SHOW UTILITIES FROM ENGINEERING PLAN ON LANDSCAPING | | | PLAN. ENSURE THAT THERE IS SUFFICIENT DISTANCE BETWEEN | | | PLANTS AND UTILITIES. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |