Plan Review Notes
Plan Review Notes For Project Z23060022
Project Number Z23060022
Review Stop PU
Sequence Number 1
Notes
Date Text
2023-07-13 12:05:39-DENOTE SIZE AND MATERIAL OF EXISTING UTILITIES
 -UNUSED LATERALS/SERVICES WILL REQUIRE REMOVAL UP TO
 MAIN
 -HARD TO DIFFERENTIATE MAINS AND SERVICES
 -SHOW ALL EXISTING AND PROPOSED VALVES AND
 APPURTENANCES
 -ENSURE 5 FOOT RADIAL CLEARANCE FOR BOTH METER BOX AND
 CLEANOUT
 -SHOW ALL EXISTING DRY UTILITIES
 -CCTV REQUIRED IN ORDER TO CONFIRM LOCATIONS OF
 EXISITNG LATERALS
 -EXHIBIT ALL UTILITY CROSSINGS BETWEN PROPOSED AND
 EXISTING UTILITIES
 -DENOTE THE DOWNSTREAM LIFT STATION THAT SERVES THE
 PROJECT AREA
 -INCLUDE LEGEND AND DATUM CONVERSION
 -PROVIDE DEMAND CALCULATIONS TO DETERMINE SUFFICIENT
 FLOW SERVED BY EXISTING PIPES
  