2023-06-01 19:17:26THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. BELVEDERE ROAD IS MAINTAINED BY PALM BEACH COUNTY.
 ANY WORK WITHIN THE RIGHT OF WAY WILL REQUIRE APPROVAL
 AND A PERMIT FROM THE COUNTY.
  
 2. LABEL THE PROPOSED R/W LINE ON ALL PLAN VIEWS.
  
 3. SHEET C-04
 A. DETAIL 4 ACCESSIBLE PARKING SPACE ADA COMPLIANT:
 SEPARATION OF WHITE AND BLUE PARALLEL STIPES SHOULD
 MATCH THE 12 INCHES SHOWN ON SHEET C-03 AS WELL AS THE
 4-INCH STRIPE CONNECTING THE ENDS OF THE PARALLEL
 STRIPES.
  
 4. SHEET C-05 DEMOLITION PLAN
 A. SHOW THE LIMITS OF THE SIDEWALK AND CURB REMOVAL
 ALONG BELVEDERE ROAD INCLUDING AT THE CORNER CURB RAMP.
 PBC TIME EXTENSION LETTER FOR PERMIT RW57085-0422
 MENTIONS INSTALLING NEW SIDEWALK ALONG THE PROJECT
 FRONTAGE (APPROX. 225 FEET).
 B. SHOW THE LIMITS OF THE REMOVAL OF THE TRAFFIC
 SEPARATOR ALONG THE NORTH CURB OF BELVEDERE ROAD.
  
 5. SHEET C-06
 A. THE DRIVEWAY APRON WITHIN THE RIGHT OF WAY SHOULD BE
 CONCRETE INSTEAD OF ASPHALT.
 B. CAN THE MOUNTABLE ISLAND WITHIN THE DRIVEWAY APRON
 BE NARROWED TO PROVIDE A WIDER SIDEWALK BEHIND IT?
 C. SUGGEST MOVING STRUCTURE NO. 2 SO THAT THE MANHOLE
 COVER IS NOT WITHIN THE WHEEL PATH AND/OR SO THAT THE
 ENTRANCE OR EXIT IS NOT BLOCKED WHEN THE MANHOLE IS
 OPENED FOR MAINTENANCE.
 D. SHOW CONCRETE SIDEWALK FOR THE FULL R/W WIDTH WEST
 OF THE DRIVEWAY.
 E. REMOVE THE CURB LINES ACROSS THE SIDEWALK AT THE
 DRIVEWAY APRON.
 F. STRUCTURE NO. 3 NEEDS TO BE COMPLETELY OUT OF THE
 PROPOSED R/W.
 G. ADJUST SPOT GRADE LEADERS SO THAT THEY LAND ON THE
 PAVEMENT INSTEAD OF ON TOP OF THE CURB.
 H. SHOW EXISTING TYPE F CURB AND GUTTER ON SECTION B-B.
 I. SHOW EXISTING TYPE F CURB AND GUTTER AND PROPOSED
 DROP CURB ON SECTION C-C.
 J. CALLOUT CONNECTION TO EXISTING CURB INLET ON PARKER
 AVE, THE PROPOSED INVERT ELEVATION, THE EXISTING BOTTOM
 ELEVATION AND WHETHER THE STRUCTURE WILL NEED TO BE
 MODIFIED TO INSTALL THE PROPOSED 15-NCH RCP.
 K. SHOULD CURBS ON THE EAST AND WEST SIDES OF THE
 DRIVEWAY TO THE ALLEY EXTEND TO THE WALLS?
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. MODIFY THE SFWMD ERP PERMIT (IF NEEDED) AND PROVIDE
 A COPY OF THE SFWMD ERP BEFORE START OF CONSTRUCTION.
  
 2. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 3. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER MANAGEMENT CALCULATIONS WILL BE
 REVIEWED WITH THE ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  