Plan Review Notes
Plan Review Notes For Project Z23050016
Project Number Z23050016
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2023-06-05 10:22:46PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ADD WATER AND SEWER DEMAND CALCULATIONS TO UTILITY
 PLAN SHEET C501.
 -SHOW AND LABEL BACKFLOW ASSEMBLY ON UTILITY PLAN.
 -EXISTING DOMESTIC WATER METER SIZE IS 2 INCH. IS SIZE
 SUFFICIENT?
 -UTILITY BILLING SYSTEM SHOWS 2 INCH FIRELINE WATER
 SERVICE AT PROPERTY. PLEASE SHOW AND LABEL IT ON PLANS.
 ALSO INDICATE IF EXISTING BUILDING HAS FIRE SPRINKLERS
 AND IF NEW BUILDING WILL NEED FIRE SPRINKLERS.
 -SURVEY SHOWS WATER PUMP NEAR WEST PROPERTY LINE.
 PLEASE INDICATE WHAT IT IS USED FOR AND IF IT IS
 CONNECTED TO A WELL. IF IT WILL REMAIN, SHOW AND LABEL
 IT ON PLANS.
 -SHOW UTILITIES ON LANDSCAPING PLAN SHEET C703. ENSURE
 NO LOCATION CONFLICTS BETWEEN PLANTS AND UTILITIES.
 -WILL IRRIGATION RUN OFF DOMESTIC WATER METER?
 -ANNUAL BACKFLOW TESTING IS SHOWING OVERDUE IN SYSTEM
 DESPITE MULTIPLE NOTICE LETTERS SENT. NEED LICENSED
 PLUMBER TO TEST IT BEFORE CONSTRUCTION STARTS.
 RESPECTFULLY,
 MARK HURLEY [email protected]
  