| Plan Review Notes For Project Z23050016 |
| Project Number |
Z23050016 |
|
| Review Stop |
PU-CS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-05 10:22:46 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -ADD WATER AND SEWER DEMAND CALCULATIONS TO UTILITY | | | PLAN SHEET C501. | | | -SHOW AND LABEL BACKFLOW ASSEMBLY ON UTILITY PLAN. | | | -EXISTING DOMESTIC WATER METER SIZE IS 2 INCH. IS SIZE | | | SUFFICIENT? | | | -UTILITY BILLING SYSTEM SHOWS 2 INCH FIRELINE WATER | | | SERVICE AT PROPERTY. PLEASE SHOW AND LABEL IT ON PLANS. | | | ALSO INDICATE IF EXISTING BUILDING HAS FIRE SPRINKLERS | | | AND IF NEW BUILDING WILL NEED FIRE SPRINKLERS. | | | -SURVEY SHOWS WATER PUMP NEAR WEST PROPERTY LINE. | | | PLEASE INDICATE WHAT IT IS USED FOR AND IF IT IS | | | CONNECTED TO A WELL. IF IT WILL REMAIN, SHOW AND LABEL | | | IT ON PLANS. | | | -SHOW UTILITIES ON LANDSCAPING PLAN SHEET C703. ENSURE | | | NO LOCATION CONFLICTS BETWEEN PLANTS AND UTILITIES. | | | -WILL IRRIGATION RUN OFF DOMESTIC WATER METER? | | | -ANNUAL BACKFLOW TESTING IS SHOWING OVERDUE IN SYSTEM | | | DESPITE MULTIPLE NOTICE LETTERS SENT. NEED LICENSED | | | PLUMBER TO TEST IT BEFORE CONSTRUCTION STARTS. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] | | | |
| |