| 2023-05-05 15:11:00 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -UTILITY BILLING SYSTEM SHOWS EXISTING WATER METER SIZE |
| | TO BE 5/8 INCH. PLEASE CONFIRM IF THAT WILL BE |
| | SUFFICIENT FOR IRRIGATION. |
| | -EXISTING METERED WATER SERVICE CURRENTLY DOES NOT HAVE |
| | AN ACTIVE USAGE BILLING ACCOUNT AND THE WATER CANNOT BE |
| | USED. ACCOUNT WOULD HAVE TO BE STARTED AND ANY FEES, |
| | CHARGES, AND DEPOSITS PAID BEFORE COULD BE USED. |
| | -VERIFY PRIVATE FIRELINE WILL NOT HAVE ANY ADDED |
| | CHEMICALS OR AUXILIARY WATER SOURCES SUCH AS WELLS. |
| | -VERIFY SLIDING GATE WILL NOT HIT FIRELINE BACKFLOW |
| | ASSEMBLY. |
| | -FIRELINE BACKFLOW ASSEMBLY WILL HAVE A CITY DETECTOR |
| | WATER METER ON IT. PROPERTY OWNER AND UTILITY ACCOUNT |
| | HOLDER MUST ALLOW ACCESS AS NEEDED TO UTILITY PERSONNEL |
| | FOR THE PURPOSES OF READING AND MAINTAINING THE METER. |
| | -ON ENGINEERING PLANS, SHOW EXISTING UTILITY EASEMENT |
| | AT EAST SIDE OF PROPERTY IF IT WILL REMAIN. ALSO SHOW |
| | UTILITY EASEMENT FOR WATER METER IF WILL BE ON PRIVATE |
| | PROPERTY. |
| | -IS A WALL ABOVE/OVER PROPOSED 2 INCH WATER SERVICE |
| | LINE? |
| | -BACKFLOW ASSEMBLY WAS INSTALLED FOR EXISTING METER, |
| | BUT NEVER INSPECTED. BEFORE EXISTING WATER SERVICE |
| | COULD BE TURNED ON AND USED, INSTALLATION WOULD NEED TO |
| | PASS INSPECTION AND THEN INTERNAL TEST WOULD BE NEEDED. |
| | CHARGES WOULD GO TO THE NEW UTILITY ACCOUNT. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| | |
| |