| Plan Review Notes For Project Z23040023 |
| Project Number |
Z23040023 |
|
| Review Stop |
PU |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-11 11:14:56 | -LIST SIZE AND MATERIAL FOR ALL EXISTING AND PROPOSED | | | UTILITIES | | | -LABEL ALL EXISTING UTILITIES WITH IN THE PROJECT SCOPE | | | DENOTE CITY'S POINT OF SERVICE | | | -PROVIDE A PROFILE FOR THE FIRE LINE FROM THE TAP TO | | | THE CITY'S POINT OF SERVICE TO ENSURE PROPER CLEARANCES | | | FOR UTILITY CONFLICTS | | | -INCLUDE TOP/BOP ELEVATIONS FOR ALL UTILITY CONFLICTS | | | -PROVIDE PROJECT ADDRESS AS WELL AS ADJACENT PARCELS | | | -SHOW ALL UNDERGROUND DRY UTILITIES WITHIN THE PROJECT | | | LIMITS | | | -TRENCH RESTORATION NEEDED PER CITY DETAIL GC-8 | | | -DENOTE THE LIFT STATION BOUNDARY THAT THE PROJECT | | | FALLS WITHIN | | | - ENSURE GATE VALVE INSTALLATION WILL BE OUTSIDE OF | | | SIDEWALK OR CURB AREAS | | | -VERIFY THAT PROPOSED SANITARY SEWER CONNECTION IS | | | DEDICATED TO PROJECT LOCATION AND NOT PROPERTY TO THE | | | SOUTH. | | | -CCTV OF MAINS ON OLIVE AND ALLEY TO THE NORTH REQUIRED | | | IN ORDER TO DETERMINE LOCATION OF EXISTING LATERALS | | | (MANHOLE TO MANHOLE) | | | -WATER MAIN CONNECTIONS IN THE ALLEY ARE TO ASBESTOS | | | CONCRETE PIPE. WHICH WOULD REQUIRE REPLACEMENT | | | -WATER METER CANNOT BE LOCATED ON PRIVATE PROPERTY | | | -FIRE HYDRANT CONNECTION MADE VIA ANCHOR TEE PER P-8 |
| |