Plan Review Notes
Plan Review Notes For Project Z23040023
Project Number Z23040023
Review Stop PU
Sequence Number 1
Notes
Date Text
2023-05-11 11:14:56-LIST SIZE AND MATERIAL FOR ALL EXISTING AND PROPOSED
 UTILITIES
 -LABEL ALL EXISTING UTILITIES WITH IN THE PROJECT SCOPE
 DENOTE CITY'S POINT OF SERVICE
 -PROVIDE A PROFILE FOR THE FIRE LINE FROM THE TAP TO
 THE CITY'S POINT OF SERVICE TO ENSURE PROPER CLEARANCES
 FOR UTILITY CONFLICTS
 -INCLUDE TOP/BOP ELEVATIONS FOR ALL UTILITY CONFLICTS
 -PROVIDE PROJECT ADDRESS AS WELL AS ADJACENT PARCELS
 -SHOW ALL UNDERGROUND DRY UTILITIES WITHIN THE PROJECT
 LIMITS
 -TRENCH RESTORATION NEEDED PER CITY DETAIL GC-8
 -DENOTE THE LIFT STATION BOUNDARY THAT THE PROJECT
 FALLS WITHIN
 - ENSURE GATE VALVE INSTALLATION WILL BE OUTSIDE OF
 SIDEWALK OR CURB AREAS
 -VERIFY THAT PROPOSED SANITARY SEWER CONNECTION IS
 DEDICATED TO PROJECT LOCATION AND NOT PROPERTY TO THE
 SOUTH.
 -CCTV OF MAINS ON OLIVE AND ALLEY TO THE NORTH REQUIRED
 IN ORDER TO DETERMINE LOCATION OF EXISTING LATERALS
 (MANHOLE TO MANHOLE)
 -WATER MAIN CONNECTIONS IN THE ALLEY ARE TO ASBESTOS
 CONCRETE PIPE. WHICH WOULD REQUIRE REPLACEMENT
 -WATER METER CANNOT BE LOCATED ON PRIVATE PROPERTY
 -FIRE HYDRANT CONNECTION MADE VIA ANCHOR TEE PER P-8