Plan Review Notes
Plan Review Notes For Project Z23040020
Project Number Z23040020
Review Stop Z
Sequence Number 2
Notes
Date Text
2023-06-20 16:59:546/20/23 - FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE A COPY OF THE LAST RECORDED WARRANTY
 DEED FOR THE SUBJECT PROPERTY. THE PROPERTY OWNER
 INFORMATION PROVIDED ON THE APPLICATION AND THE
 OWNER???S CONSENT FORM DO NOT MATCH THE PROPERTY OWNER
 INFORMATION IN THE WARRANTY DEED SUBMITTED. [NOT
 SATISFIED]
 G. PLEASE PROVIDE AN ELECTRONIC COPY OF THE SURVEY.
 [SATISFIED]
 H. PLEASE PROVIDE AN ENGINEERING
 (WATER/WASTEWATER-SPECIFIC) PLAN. [SATISFIED]
 I. PLEASE PROVIDE PHYSICAL HARDCOPIES OF THE LANDSCAPE
 PLANS. [SATISFIED]
 J. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [NOT
 SATISFIED]
 K. PLEASE PROVIDE A SCHOOL CAPACITY AVAILABILITY
 DETERMINATION (SCAD) PROVIDED BY THE SCHOOL DISTRICT OF
 PALM BEACH COUNTY FOR THE SUBJECT PROJECT. [NOT
 SATISFIED]
 L. PLEASE PROVIDE THE CITY SERVICE AND PUBLIC UTILITY
 LETTERS (FROM FLORIDA PUBLIC UTILITIES, FLORIDA POWER &
 LIGHT COMPANY, AND COMCAST CABLE COMMUNICATION) FOR THE
 SUBJECT PROJECT. [NOT SATISFIED]
 M. IF A REZONING OF THE SUBJECT PROPERTY IS BEING
 REQUESTED, THEN A SEPARATE REZONING TYPE OF APPLICATION
 MUST BE SUBMITTED. [NOT SATISFIED]
 N. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 O. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [NOT SATISFIED]
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. IN REFERENCE TO REVIEW COMMENT M., THE PLANS
 SUBMITTED INDICATE A PROPOSED REZONING OF THE SUBJECT
 PROPERTY. THEREFORE, PLEASE CONFIRM IF A REZONING IS
 BEING REQUESTED. IF SO, A SEPARATE REZONING TYPE OF
 APPLICATION MUST BE SUBMITTED. IF NOT, PLEASE CORRECT
 THE INFORMATION INDICATED IN THE PLANS ACCORDINGLY.
 [NOT SATISFIED]
 2. IN ACCORDANCE WITH RESOLUTION NO. 306-22, THE MF32
 ZONING DISTRICT BUILDING HEIGHT REGULATIONS APPLY TO
 THE PROPOSED PROJECT. BASED ON THE CITY???S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR) SECTION
 94-77(A)(3), THE PROPOSED PROJECT IS IN COMPLIANCE WITH
 THE MAXIMUM BUILDING HEIGHT ALLOWANCE OF THE MF32
 ZONING DISTRICT. THEREFORE, PLEASE SUBMIT A REVISED
 JUSTIFICATION LETTER BECAUSE THE REQUESTED VARIANCE TO
 THE MAXIMUM BUILDING HEIGHT ALLOWANCE IS NOT NECESSARY.
 [SATISFIED]
 3. PLEASE IDENTIFY/INDICATE THE EXISTING/PROPOSED
 EASEMENTS ON THE PLANS. [NOT SATISFIED]
 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED PUBLIC ART ON THE PLANS. [WITHDRAWN]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING AND PROPOSED FIRE HYDRANTS WITHIN 250 FEET
 OF THE PROPOSED STRUCTURES ON THE PLANS. [SATISFIED]
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED SPECIAL UTILITY STRUCTURES / ABOVE GROUND
 APPURTENANCES ON THE PLANS. [PARTIALLY SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND INTENSITY OF THE PROPOSED OUTDOOR
 ILLUMINATION ON THE PLANS. [PARTIALLY SATISFIED]
 8. IN ACCORDANCE WITH THE ZLDR SECTION 94-485(Q),
 PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED BICYCLE PARKING FACILITIES ON THE PLANS.
 IDENTIFY/INDICATE THE PROPOSED NUMBER OF BICYCLE
 PARKING IN THE PARKING TABULATION. [PARTIALLY
 SATISFIED]
 9. IN REGARDS TO THE PROVIDED JUSTIFICATION LETTER FOR
 THE PARKING REQUIREMENTS, THE SUBJECT PROPERTY IS NOT
 LOCATED WITHIN THE CITY CENTER DISTRICT. THE CITYWIDE
 DISTRICT SPECIFIC MINIMUM PARKING REQUIREMENTS APPLY TO
 THE PROPOSED PROJECT. THEREFORE, PLEASE REVISE THE
 SUBJECT JUSTIFICATION LETTER. [NOT SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF THE DRIVEWAYS, CURB CUTS, AND TURNING LANES ADJACENT
 TO OR ACROSS FROM THE SUBJECT PROPERTY ON THE PLANS.
 [NOT SATISFIED]
 11. PLEASE PROVIDE THE STANDARD CITY DETAILS/ELEVATIONS
 OF THE PROPOSED BICYCLE PARKING ON THE PLANS. [NOT
 SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING AND PROPOSED PUBLIC TRANSIT FACILITIES
 WITHIN THE IMMEDIATE VICINITY OF THE SUBJECT PROPERTY
 ON THE PLANS. [NOT SATISFIED]
 13. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 IDENTIFY/INDICATE THE PROPOSED NUMBER OF AFFORDABLE
 DESIGNATED DWELLING UNITS IN THE SITE CALCULATIONS.
 [NOT SATISFIED]
 14. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 PROVIDE THE DENSITY CALCULATIONS IN THE SITE
 CALCULATIONS. [NOT SATISFIED]
 15. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 CONFIRM THE RESTRICTED UNIT???S AFFORDABILITY PERIOD.
 [SATISFIED]
 16. PLEASE PROVIDE CONSISTENT INFORMATION ON THE SITE
 PLAN (SHEET NO. SP-1) AND ARCHITECTURAL SITE PLAN
 (SHEET NO. A100.00) FOR RESUBMITTAL OR DO NOT PROVIDE
 AN ARCHITECTURAL SITE PLAN AS PART OF THE RESUBMITTAL.
 [NOT SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 17. IN REFERENCE TO PREVIOUS REVIEW COMMENT 6., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION
 REGARDING THE LOCATION OF THE PROPOSED SPECIAL UTILITY
 STRUCTURES / ABOVE GROUND APPURTENANCES ON THE SITE
 PLANS, LANDSCAPE PLANS, AND UTILITIES PLANS.
 18. IN REFERENCE TO PREVIOUS REVIEW COMMENT 7., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION
 REGARDING THE LOCATION, HEIGHT, AND INTENSITY OF THE
 PROPOSED OUTDOOR ILLUMINATION ON THE SITE PLANS,
 LANDSCAPE PLANS, AND UTILITIES PLANS.
 19. IN REFERENCE TO PREVIOUS REVIEW COMMENT 8., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION
 REGARDING THE LOCATION OF THE PROPOSED BICYCLE PARKING
 FACILITIES ON THE SITE PLANS AND LANDSCAPE PLANS.
 PLEASE CORRECT THE REQUIRED NUMBER OF BICYCLE PARKING
 INFORMATION IN THE PARKING TABULATION.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  