| Date |
Text |
| 2023-06-23 15:19:39 | -PLEASE PROVIDE CIVIL DRAWINGS MENTIONED IN SITE PLAN |
| | SHEET |
| | -PROVIDE CCTV OF ALL EXISTING SANITARY SEWER MAIN |
| | FRONTING PROJECT LIMITS BEFORE AND AFTER CONSTRUCTION. |
| | -PROVIDE SOFTDIG INFORMATION AT PROPOSED POINT OF |
| | CONNECTION |
| | -REFER TO THE CITY???S STANDARD DETAILS FOR PLACEMENT |
| | OF DDCA AND CITY???S POINT OF SERVICE (POS) WHICH |
| | REQUIRES A SECOND VALVE AT R/W |
| | -SET UP ALL PLAN SHEETS TO PRINT TO SCALE ON 11X17 |
| | -SHOW ALL EXISTING WATER SERVICES/METER BOXES/VALVES |
| | VAULTS, AND SANITARY SEWER LATERALS WITHIN PROJECT |
| | LIMITS. |
| | -ALL EXISTING VALVES AND MANHOLES NEED TO BE LEGIBLE |
| | -SHOW EXISTING VALVES AND APPURTENANCES AND CORRECT |
| | ALIGNMENT OF EXISTING CITY-MAINTAINED UTILITIES |
| | -LABEL ALL UTILITIES TO BE MAINTAINED ON-SITE BY OWNER |
| | ENTITY AS ???PRIVATE???, AS APPLICABLE |
| | -ALL PROPOSED UTILITY EASEMENTS AND PLACEMENT OF |
| | DOMESTIC WATER METER/BACKFLOW PREVENTER ASSEMBLY NOT IN |
| | COMPLIANCE WITH APPLICABLE CITY???S STANDARD DETAILS |
| | WILL REQUIRE WATER DISTRIBUTION???S APPROVAL. PROVIDE 5 |
| | FOOT RADIAL CLEARANCE IN ALL DIRECTIONS. |
| | -ALL PROPOSED UTILITY EASEMENTS AND PLACEMENT OF |
| | CLEANOUT NOT IN COMPLIANCE WITH APPLICABLE CITY???S |
| | STANDARD DETAILS WILL REQUIRE SANITARY COLLECTIONS |
| | APPROVAL. PROVIDE 5 FOOT RADIAL CLEARANCE IN ALL |
| | DIRECTIONS. |
| | -PROVIDE PROFILES FOR ALL CONNECTIONS TO EXISTING |
| | CITY-MAINTAINED UTILITIES FROM THE POINT OF CONNECTION |
| | TO THE POINT OF SERVICE. |
| | -ON PROFILE VIEW, SHOW ALL EXISTING AND PROPOSED |
| | UTILITIES (CITY-MAINTAINED AND DRY UTILITIES), CALL OUT |
| | UTILITY TYPE, DIMENSIONS, PIPE MATERIAL, AND VERTICAL |
| | CLEARANCE OD TO OD AT EACH UTILITY CROSSING. |
| | -PROVIDE DIMENSIONS BETWEEN PROPOSED UTILITIES TO |
| | ENSURE PROPER HORIZONTAL CLEARANCE |
| | --SINGLE WATER TAPS SERVING DOMESTIC, FIRE LINE, |
| | IRRIGATION, AND FIRE HYDRANT PRESENTS ISSUES FOR FUTURE |
| | MAINTENANCE/REPAIRS/REPLACEMENTS ETC. AS SHUTDOWN WILL |
| | DISRUPT SERVICE |
| | -SHOW ALL UTILITY CROSSINGS WITH HORIZONTAL AND |
| | VERTICAL SEPARATION, AS WELL AS SPECIFYING THE UTILITY |
| | TYPE, SIZE, AND MATERIAL. |
| | -PROVIDE LOS CALCULATIONS, AS WELL AS CHANGE IN DEMAND |
| | BETWEEN EXISTING CONDITIONS AND PROPOSED CONDITIONS. |
| | -PROVIDE PROJECT FACT SHEET |
| | -EXISTING WATER AND SEWER SERVICES CURRENTLY SERVING |
| | THE PROPERTY, IF NOT USED, NEED TO BE CUT AND CAP AT |
| | MAIN. REMOVAL IS REQUIRED IF LARGER THAN 2??? IN |
| | DIAMETER, OR AS REQUIRED BY THE RIGHT-OF-WAY???S |
| | GOVERNING AGENCY. |
| | -INCLUDE LEGEND, DATUM CONVERSION, AND NORTH ARROW ON |
| | PLANS |
| | -PROPOSED SEWER LATERALS LARGER THAN 6??? WILL REQUIRE |
| | CONNECTION A MANHOLE, WITH A CLEANOUT OF THE SAME SIZE |
| | INSTALLED AS THE CITY???S POS. |
| | -ADD NOTE TO PLANS SPECIFYING THE LIFT STATION THAT THE |
| | PROJECT IS UPSTREAM FROM. |
| | -PROVIDE A BLOW-UP DETAIL FOR ALL CONNECTION POINTS TO |
| | CITY-MAINTAINED UTILITIES. |
| |
Print |