| | 1. SHOW AND LABEL ANY EXISTING OR PROPOSED WATER |
| | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING |
| | TO THEM- WATER MAIN INFORMATION IS NOT SHOWN ON SP-010 |
| | 2. SHOW EXISTING AND PROPOSED DEDICATED UTILITY |
| | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO |
| | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO |
| | STRUCTURES WITHIN THE EASEMENT- EASEMENTS CAN???T BE |
| | FOUND ON PLANS |
| | 3. PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION |
| | OF WATER METER AND BACKFLOW PREVENTION. |
| | 4. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD |
| | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE |
| | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND |
| | MATERIAL LOCATED IN THE RIGHT-OF-WAY. |
| | 5. SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY |
| | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT |
| | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING |
| | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| | PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. |
| | 6. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG |
| | ENTIRE PROJECT FRONTAGE (CONDITION OF SITE PLAN |
| | APPROVAL) |
| | 7. ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM |
| | LIFT STATION NUMBER. |
| | |
| | |
| |