| Date |
Text |
| 2023-05-05 13:06:39 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -ON SITE PLAN S-1, ARE THE BUILDINGS EXISTING OR |
| | PROPOSED? |
| | -IN RESUBMITTAL PACKAGE, ADD COPIES OF SURVEY AND |
| | WATER/SEWER PLANS. WILL PROVIDE MORE REVIEW COMMENTS |
| | ONCE ABLE TO REVIEW THOSE. |
| | -UTILITY BILLING SYSTEM SHOWS AN EXISTING 1 INCH |
| | DOMESTIC WATER METER AT THE PROPERTY. |
| | -BELOW IS A LIST OF SOME STANDARD REVIEW COMMENTS THAT |
| | MAY ASSIST YOU: |
| | *EXISTING AND PROPOSED METERED WATER SERVICES SHOWN AND |
| | LABELED. |
| | *DOMESTIC BACKFLOW ASSEMBLIES SHOULD BE LOCATED ON |
| | PRIVATE PROPERTY OUTSIDE OF ANY UTILITY EASEMENTS AND |
| | ADJACENT TO PROPERTY/ROW LINE WITH PIPE DISTANCE |
| | MINIMIZED TO METER. |
| | *DOMESTIC BACKFLOW ASSEMBLIES LABELED WITH ???RP??? |
| | TYPE AND SIZE. |
| | *FIRELINE BACKFLOW ASSEMBLY LABELED WITH TYPE (DCDA OR |
| | RPDA) AND SIZE. IF DCDA TYPE PROPOSED, NEED |
| | VERIFICATION PRIVATE FIRE SYSTEM WILL HAVE NO ADDED |
| | CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS. |
| | *WATER METERS LABELED WITH SIZE AND USE TYPE |
| | (DOMESTIC/IRRIGATION). METERS 3 INCHES OR LARGER |
| | LABELED ???ABOVE-GROUND???. |
| | *PROPERTY LINES, EASEMENTS, TRANSFORMERS, GREASE TRAPS, |
| | RIGHT OF WAYS, GUY ANCHOR WIRES, STREETS, FENCES, |
| | WALLS, POLES, FRANCHISE UTILITIES, SIDEWALKS, SIGNS, |
| | FDCS, DRIVEWAYS, CLEANOUTS, SANITARY SEWER LATERALS, |
| | AND STRUCTURES SHOWN AND LABELED. |
| | *FIRE SPRINKLERS MAY NOT RUN OFF DOMESTIC WATER METERS |
| | AND NEEDS TO BE ON A SEPARATE WATER SERVICE WITH |
| | DETECTOR STYLE BACKFLOW ASSEMBLY. IF NO FIRE SERVICE |
| | SHOWN ON PLANS, NEED VERIFICATION NO FIRE SPRINKLERS |
| | WILL BE IN BUILDINGS. |
| | *PLANS SHOULD HAVE NORTH DIRECTION ARROW, VISUAL SCALE |
| | MEASUREMENT ICON / GRAPHIC SCALE, ADDRESS, AND DATE. |
| | *DOMESTIC WATER METERS NOT LOCATED IN BUILDINGS OR |
| | DRIVEWAYS. PREFERRED LOCATION IN LANDSCAPE (NOT |
| | HARDSCAPE) ADJACENT PROPERTY LINE WITH DISTANCE |
| | MINIMIZED TO RIGHT OF WAY AND WATER MAIN. |
| | *ALL INSTALLED CONTAINMENT BACKFLOW ASSEMBLIES MUST BE |
| | LEAD-FREE AND USC-APPROVED (BY SIZE, MAKE, MODEL, |
| | ORIENTATION, VALVING, AND BYPASS). |
| | *TREES, TREE ROOTS, AND BUSHES NOT ENCROACHING ON WATER |
| | METERS AND BACKFLOW ASSEMBLIES. SHOW METERED WATER |
| | SERVICES AND BACKFLOW ASSEMBLIES ON |
| | LANDSCAPING/PLANTING PLANS. |
| | *FIRELINE BACKFLOW ASSEMBLY SHOULD BE INSTALLED ON |
| | PRIVATE PROPERTY OUTSIDE OF ANY UTILITY EASEMENTS AT A |
| | LOCATION COMPLIANT WITH FIRE CODE AND MINIMIZING PIPE |
| | DISTANCE TO WATER MAIN (ADJACENT PROPERTY/ROW LINE |
| | WHENEVER POSSIBLE). |
| | *POLES AND STRUCTURES MINIMUM 3 FEET AWAY FROM WATER |
| | METER BOXES. |
| | *DOMESTIC WATER METERS ACCESSIBLE FROM RIGHT OF WAY AND |
| | NOT LOCKED BEHIND ANY GATES, FENCES, OR WALLS. |
| | *WATER METERS 6 INCH OR LARGER NEED BE ACCESSIBLE AND |
| | REPLACEABLE BY FORD F350 CRANE TRUCK. |
| | *WATER METERS 8 INCHES AND LARGER ARE NOT STOCKED AND |
| | HAVE TO BE ORDERED AFTER UTILITY QUOTE IS PAID. LEAD |
| | TIMES MAY BE OVER 6 MONTHS FROM TIME OF PAYMENT. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| | |
| |