Plan Review Notes
Plan Review Notes For Project Z23040020
Project Number Z23040020
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2023-05-05 13:06:39PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ON SITE PLAN S-1, ARE THE BUILDINGS EXISTING OR
 PROPOSED?
 -IN RESUBMITTAL PACKAGE, ADD COPIES OF SURVEY AND
 WATER/SEWER PLANS. WILL PROVIDE MORE REVIEW COMMENTS
 ONCE ABLE TO REVIEW THOSE.
 -UTILITY BILLING SYSTEM SHOWS AN EXISTING 1 INCH
 DOMESTIC WATER METER AT THE PROPERTY.
 -BELOW IS A LIST OF SOME STANDARD REVIEW COMMENTS THAT
 MAY ASSIST YOU:
 *EXISTING AND PROPOSED METERED WATER SERVICES SHOWN AND
 LABELED.
 *DOMESTIC BACKFLOW ASSEMBLIES SHOULD BE LOCATED ON
 PRIVATE PROPERTY OUTSIDE OF ANY UTILITY EASEMENTS AND
 ADJACENT TO PROPERTY/ROW LINE WITH PIPE DISTANCE
 MINIMIZED TO METER.
 *DOMESTIC BACKFLOW ASSEMBLIES LABELED WITH ???RP???
 TYPE AND SIZE.
 *FIRELINE BACKFLOW ASSEMBLY LABELED WITH TYPE (DCDA OR
 RPDA) AND SIZE. IF DCDA TYPE PROPOSED, NEED
 VERIFICATION PRIVATE FIRE SYSTEM WILL HAVE NO ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS.
 *WATER METERS LABELED WITH SIZE AND USE TYPE
 (DOMESTIC/IRRIGATION). METERS 3 INCHES OR LARGER
 LABELED ???ABOVE-GROUND???.
 *PROPERTY LINES, EASEMENTS, TRANSFORMERS, GREASE TRAPS,
 RIGHT OF WAYS, GUY ANCHOR WIRES, STREETS, FENCES,
 WALLS, POLES, FRANCHISE UTILITIES, SIDEWALKS, SIGNS,
 FDCS, DRIVEWAYS, CLEANOUTS, SANITARY SEWER LATERALS,
 AND STRUCTURES SHOWN AND LABELED.
 *FIRE SPRINKLERS MAY NOT RUN OFF DOMESTIC WATER METERS
 AND NEEDS TO BE ON A SEPARATE WATER SERVICE WITH
 DETECTOR STYLE BACKFLOW ASSEMBLY. IF NO FIRE SERVICE
 SHOWN ON PLANS, NEED VERIFICATION NO FIRE SPRINKLERS
 WILL BE IN BUILDINGS.
 *PLANS SHOULD HAVE NORTH DIRECTION ARROW, VISUAL SCALE
 MEASUREMENT ICON / GRAPHIC SCALE, ADDRESS, AND DATE.
 *DOMESTIC WATER METERS NOT LOCATED IN BUILDINGS OR
 DRIVEWAYS. PREFERRED LOCATION IN LANDSCAPE (NOT
 HARDSCAPE) ADJACENT PROPERTY LINE WITH DISTANCE
 MINIMIZED TO RIGHT OF WAY AND WATER MAIN.
 *ALL INSTALLED CONTAINMENT BACKFLOW ASSEMBLIES MUST BE
 LEAD-FREE AND USC-APPROVED (BY SIZE, MAKE, MODEL,
 ORIENTATION, VALVING, AND BYPASS).
 *TREES, TREE ROOTS, AND BUSHES NOT ENCROACHING ON WATER
 METERS AND BACKFLOW ASSEMBLIES. SHOW METERED WATER
 SERVICES AND BACKFLOW ASSEMBLIES ON
 LANDSCAPING/PLANTING PLANS.
 *FIRELINE BACKFLOW ASSEMBLY SHOULD BE INSTALLED ON
 PRIVATE PROPERTY OUTSIDE OF ANY UTILITY EASEMENTS AT A
 LOCATION COMPLIANT WITH FIRE CODE AND MINIMIZING PIPE
 DISTANCE TO WATER MAIN (ADJACENT PROPERTY/ROW LINE
 WHENEVER POSSIBLE).
 *POLES AND STRUCTURES MINIMUM 3 FEET AWAY FROM WATER
 METER BOXES.
 *DOMESTIC WATER METERS ACCESSIBLE FROM RIGHT OF WAY AND
 NOT LOCKED BEHIND ANY GATES, FENCES, OR WALLS.
 *WATER METERS 6 INCH OR LARGER NEED BE ACCESSIBLE AND
 REPLACEABLE BY FORD F350 CRANE TRUCK.
 *WATER METERS 8 INCHES AND LARGER ARE NOT STOCKED AND
 HAVE TO BE ORDERED AFTER UTILITY QUOTE IS PAID. LEAD
 TIMES MAY BE OVER 6 MONTHS FROM TIME OF PAYMENT.
 RESPECTFULLY,
 MARK HURLEY [email protected]
  
  Print


Account Summary | Usage Policy | Privacy Policy