| 2023-06-02 11:35:34 | 6/2/23 ??? FAILED |
| | |
| | |
| | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN |
| | RESUBMITTING: |
| | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL |
| | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. |
| | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED |
| | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG |
| | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). |
| | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO |
| | ADDITIONAL COMMENTS. |
| | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE |
| | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE |
| | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL |
| | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. |
| | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) |
| | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF |
| | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED |
| | AFTER THE FIRST RESUBMITTAL. |
| | |
| | REQUIRED MATERIALS MUST BE PROVIDED: |
| | F. PLEASE PROVIDE PROOF OF AN APPROVED AND RECORDED |
| | UNITY OF TITLE OF THE TWO (2) PARCELS (PER CONDITION |
| | NO. 1 OF THE CLASS B SPECIAL USE PERMIT ??? ZONING |
| | BOARD OF APPEALS CASE NO. (ZBA) 3418). |
| | G. PLEASE PROVIDE A CURRENT SURVEY. |
| | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW |
| | COMMENTS BELOW. |
| | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT |
| | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED |
| | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. |
| | |
| | REVIEW COMMENT MUST BE ADDRESSED: |
| | 1. IT HAS BEEN IDENTIFIED THAT THE APPROXIMATELY |
| | 12-FOOT WIDE BY 50-FOOT LONG AREA EAST OF THE EXISTING |
| | BUILDING IS NOT A PART OF THE PRIVATE PROPERTY, |
| | THEREFORE, PLEASE PROVIDE A CURRENT SURVEY AND REVISED |
| | PLANS. |
| | 2. PLEASE IDENTIFY/INDICATE THE EXISTING/PROPOSED |
| | EASEMENTS ON THE PLANS. |
| | 3. IT HAS BEEN IDENTIFIED THAT THE BUILDING FOOTPRINT |
| | ON THE PROPOSED FLOOR PLAN (SHEET NUMBER A1.0) AND THE |
| | OTHER PLANS PROVIDED DO NOT MATCH. THEREFORE, PLEASE |
| | REVISE THE PLANS, ACCORDINGLY. |
| | 4. PLEASE IDENTIFY/INDICATE HOGANS STREET ON THE PLANS, |
| | ACCORDINGLY. |
| | 5. IT HAS BEEN IDENTIFIED THAT THE PROPOSED 70-DEGREE |
| | ANGLED PARKING SPACES (STANDARD AND ADA) ARE NOT IN |
| | COMPLIANCE WITH THE MINIMUM OFF-STREET PARKING |
| | DIMENSIONAL REQUIREMENTS OF THE ZLDR SUBSECTION |
| | 94-485(N), THEREFORE PLEASE REVISE THE PLANS, |
| | ACCORDINGLY. |
| | 6. IT HAS BEEN IDENTIFIED THAT THE PROPOSED WALL |
| | (DEMONSTRATED ON PARCEL NUMBER 74434316150010070) IS |
| | CLOSER THAN THE MINIMUM SIX (6) INCHES DISTANCE |
| | REQUIREMENT ALONG THE SIDE LOT LINE ACCORDING TO THE |
| | ZLDR SUBSECTION 94-273(D)(54)(B)(14), THEREFORE PLEASE |
| | REVISE THE PLANS, ACCORDINGLY. |
| | 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE VISIBILITY |
| | TRIANGLE AREAS/DIMENSIONS AND |
| | IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED WALLS |
| | OUTSIDE OF THESE AREAS ON THE DIFFERENT PLANS ACCORDING |
| | TO THE ZLDR SUBSECTION 94-305(E). |
| | 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, |
| | HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON THE |
| | PLANS, ACCORDINGLY. |
| | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF |
| | THE EXISTING AND PROPOSED FIRE HYDRANTS WITHIN 250 FEET |
| | OF THE PROPOSED STRUCTURE ON THE PLANS. |
| | 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION |
| | OF THE PROPOSED PUBLIC ART ON THE PLANS. |
| | 11. PLEASE IDENTIFY/INDICATE THE FUTURE LAND USE |
| | DESIGNATIONS IN THE SITE TABULAR DATA ON SHEET NUMBER |
| | SP-1 OF 1. |
| | 12. PLEASE IDENTIFY/INDICATE SEPARATE AREA |
| | ACREAGE/SQUARE FOOTAGE CALCULATIONS FOR BOTH PARCEL |
| | NUMBERS 74-43-43-16-15-001-0010 AND |
| | 74-43-43-16-15-001-0070 IN THE SITE TABULAR DATA ON |
| | SHEET NUMBER SP-1 OF 1. |
| | 13. PLEASE IDENTIFY/INDICATE THE EXISTING IMPERMEABLE |
| | SURFACE LOT COVERAGE SQUARE FOOTAGE AND PERCENTAGE |
| | CALCULATION IN RELATION TO PARCEL NUMBER |
| | 74-43-43-16-15-001-0010 IN THE SITE TABULAR DATA ON |
| | SHEET NUMBER SP-1 OF 1. |
| | 14. PLEASE IDENTIFY/INDICATE THE PROPOSED IMPERMEABLE |
| | SURFACE LOT COVERAGE SQUARE FOOTAGE AND PERCENTAGE |
| | CALCULATION IN RELATION TO PARCEL NUMBER |
| | 74-43-43-16-15-001-0010 IN THE SITE TABULAR DATA ON |
| | SHEET NUMBER SP-1 OF 1. |
| | 15. PLEASE IDENTIFY/INDICATE THE PROPOSED OPEN SPACE |
| | AREA SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN |
| | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN |
| | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. |
| | 16. PLEASE IDENTIFY/INDICATE THE PROPOSED LANDSCAPE |
| | SPACE AREA SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN |
| | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN |
| | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. |
| | 17. PLEASE IDENTIFY/INDICATE THE EXISTING BUILDING LOT |
| | COVERAGE SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN |
| | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN |
| | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. |
| | 18. PLEASE IDENTIFY/INDICATE THE PROPOSED BUILDING LOT |
| | COVERAGE SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN |
| | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN |
| | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. |
| | 19. PLEASE IDENTIFY/INDICATE THE EXISTING BUILDING |
| | FLOOR AREA SQUARE FOOTAGE CALCULATION IN RELATION TO |
| | PARCEL NUMBER 74-43-43-16-15-001-0010 IN THE SITE |
| | TABULAR DATA ON SHEET NUMBER SP-1 OF 1. |
| | 20. PLEASE IDENTIFY/INDICATE THE PROPOSED BUILDING |
| | FLOOR AREA SQUARE FOOTAGE CALCULATION IN RELATION TO |
| | PARCEL NUMBER 74-43-43-16-15-001-0010 IN THE SITE |
| | TABULAR DATA ON SHEET NUMBER SP-1 OF 1. |
| | 21. PLEASE REVISE THE PROPERTY DEVELOPMENT REQUIREMENTS |
| | TABLE ON SHEET NUMBER SP-1OF 1 BY SEPARATING OUT THE |
| | CODE REQUIREMENTS FOR THE MF14 AND GC ZONING DISTRICTS. |
| | |
| | |
| | KEVIE DEFRANC |
| | SENIOR PLANNER ??? PLANNING DIVISION |
| | [email protected] |
| | 561-822-1449 |
| | |
| |