| 2023-06-29 12:24:02 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -PROPOSED PRIVATE FIRE HYDRANT APPEARS TO BE TEED OFF |
| | DOMESTIC PLUMBING LINE. SHOULD CONNECT TO FIRELINE |
| | INSTEAD. |
| | -FOR PRIOR REVIEW COMMENT AND RESPONSE: SHOW ALL |
| | EXISTING METERED WATER SERVICES, FIRE HYDRANTS, AND |
| | BACKFLOW ASSEMBLIES AND LABEL WHAT IS HAPPENING TO |
| | THEM. AT LEAST A LARGE DDCV, SMALL RP, AND FIRE HYDRANT |
| | ARE MISSING FROM THE SOUTH AREA OF PROPERTY AS WELL AS |
| | A METER AND SMALL RP COMMENT RESPONSE: ALL KNOWN |
| | EXISTING WATER SERVICES, FIRE HYDRANTS, AND BACKFLOW |
| | ASSEMBLIES FROM ASBUILT AND SURVEY HAVE BEEN LABELED TO |
| | SHOW WHAT IS HAPPENING TO THEM. SEE WATER AND SEWER |
| | SHEET, C04. |
| | NOT SATISFIED: NEED TO SHOW AND LABEL THE MISSING |
| | EXISTING DOMESTIC AND FIRE BACKFLOW ASSEMBLIES ON |
| | ENGINEERING PLANS. ALSO NEED TO SHOW THE EXISTING WATER |
| | SERVICES. MAY NEED TO DO SITE VISIT IF ASBUILT AND |
| | SURVEY DO NOT SHOW THEM. IF NEED ASSISTANCE LOCATING |
| | THEM, CAN CONTACT [email protected] |
| | -RELOCATED FIRE HYDRANT IS SHOWN FAR FROM WATER MAIN |
| | AND NOT PROTECTED BY BACKFLOW ASSEMBLY. UPON FURTHER |
| | REVIEW AT ENGINEERING DEVELOPMENT SUBMITTAL, MAY BE |
| | REQUIRED TO RELOCATE THE FIRE HYDRANT CLOSER TO WATER |
| | MAIN OR ADD FIRELINE BACKFLOW ASSEMBLY. |
| | -CANNOT HAVE WALL BUILT OVER PROPOSED WATER SERVICE |
| | LINE AND NEED ACCESS TO METERS. REROUTE WALL AROUND THE |
| | METERED WATER SERVICES AND BACKFLOW ASSEMBLIES. |
| | -CANNOT HAVE PROPOSED WALL BUILT OVER PIPE TO FIRE |
| | HYDRANT. REROUTE WALL AROUND HYDRANT. ENSURE MEETING |
| | THE REQUIRED CLEARANCE DISTANCES. |
| | -WALLS MAY NEED TO BE REROUTED AROUND OTHER WATER |
| | SERVICES ONCE THEY ARE SHOWN AND LABELED ON PLANS. |
| | RESPECTFULLY, |