| 2023-05-11 07:33:26 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -BACKFLOW ASSEMBLIES ARE EXCESSIVELY FAR FROM THE |
| | PROPERTY LINE. REFER TO WATER SERVICE STANDARD DETAILS |
| | LOCATION GUIDANCE. |
| | -ADD SIZE TO LABELS OF PROPOSED WATER METERS AND |
| | BACKFLOW ASSEMBLIES. |
| | -WATER METERS 3 INCH OR LARGER NEED TO BE INSTALLED |
| | ABOVE-GROUND PER STANDARD DETAIL WS3. |
| | -ADD WORDING PRIVATE TO LABEL OF FIRE HYDRANT |
| | DOWNSTREAM OF DDCV. |
| | -ADD WATER AND SEWER DEMAND CALCULATIONS TO WATER AND |
| | SEWER PLAN. |
| | -SHOW ALL EXISTING METERED WATER SERVICES, FIRE |
| | HYDRANTS, AND BACKFLOW ASSEMBLIES AND LABEL WHAT IS |
| | HAPPENING TO THEM. AT LEAST A LARGE DDCV, SMALL RP, AND |
| | FIRE HYDRANT ARE MISSING FROM THE SOUTH AREA OF |
| | PROPERTY AS WELL AS A METER AND SMALL RP |
| | -NEAR THE SOUTH PROPERTY LINE, THERE ARE SOME LARGE |
| | MECHANICAL PUMPS. PLEASE DESCRIBE WHAT THEY ARE USED |
| | FOR. |
| | -CLEARLY SHOW AND LABEL FIRE HYDRANTS ON WATER PLAN. |
| | -IF THERE WILL BE ANY ELECTRIC TRANSFORMERS WITH |
| | CONCRETE PADS, THEN SHOW AND LABEL ON ENGINEERING |
| | PLANS. |
| | -VERIFY PRIVATE FIRE SYSTEM WILL HAVE NO ADDED |
| | CHEMICALS OR AUXILIARY WATER SOURCES SUCH AS WELLS. |
| | -WILL THE FITNESS CENTER HAVE ANY FOOD SERVICE |
| | REQUIRING A GREASE TRAP? IF SO, AND IT IS LOCATED |
| | OUTSIDE, THEN SHOW AND LABEL ON SEWER PLAN. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |