Plan Review Notes
Plan Review Notes For Project Z23040016
Project Number Z23040016
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2023-05-11 07:33:26PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -BACKFLOW ASSEMBLIES ARE EXCESSIVELY FAR FROM THE
 PROPERTY LINE. REFER TO WATER SERVICE STANDARD DETAILS
 LOCATION GUIDANCE.
 -ADD SIZE TO LABELS OF PROPOSED WATER METERS AND
 BACKFLOW ASSEMBLIES.
 -WATER METERS 3 INCH OR LARGER NEED TO BE INSTALLED
 ABOVE-GROUND PER STANDARD DETAIL WS3.
 -ADD WORDING PRIVATE TO LABEL OF FIRE HYDRANT
 DOWNSTREAM OF DDCV.
 -ADD WATER AND SEWER DEMAND CALCULATIONS TO WATER AND
 SEWER PLAN.
 -SHOW ALL EXISTING METERED WATER SERVICES, FIRE
 HYDRANTS, AND BACKFLOW ASSEMBLIES AND LABEL WHAT IS
 HAPPENING TO THEM. AT LEAST A LARGE DDCV, SMALL RP, AND
 FIRE HYDRANT ARE MISSING FROM THE SOUTH AREA OF
 PROPERTY AS WELL AS A METER AND SMALL RP
 -NEAR THE SOUTH PROPERTY LINE, THERE ARE SOME LARGE
 MECHANICAL PUMPS. PLEASE DESCRIBE WHAT THEY ARE USED
 FOR.
 -CLEARLY SHOW AND LABEL FIRE HYDRANTS ON WATER PLAN.
 -IF THERE WILL BE ANY ELECTRIC TRANSFORMERS WITH
 CONCRETE PADS, THEN SHOW AND LABEL ON ENGINEERING
 PLANS.
 -VERIFY PRIVATE FIRE SYSTEM WILL HAVE NO ADDED
 CHEMICALS OR AUXILIARY WATER SOURCES SUCH AS WELLS.
 -WILL THE FITNESS CENTER HAVE ANY FOOD SERVICE
 REQUIRING A GREASE TRAP? IF SO, AND IT IS LOCATED
 OUTSIDE, THEN SHOW AND LABEL ON SEWER PLAN.
 RESPECTFULLY,