Notes
Date Text
2023-06-16 16:46:55-ENSURE THAT 36" MAIN IS SENTERED BETWEEN EXISTING
 EASEMENT. PLAN VIEW MAKES IT APPEAR AS IF MAIN IS ON
 EASTERN BIRDER OF EASEMENT.
 -CONSIDER THE DEPTH OF THE 36" MAIN WHEN MILLING AND
 RESURFACING, AS WELL AS OTHER PHASES OF CONSTRUCTION.
 AVIBRATION IMPACT STUDY MAY BE NEEDED.
 -COMMENT 6 NOT FULLY ADDRESSED. SOME CROSSING INFO
 STILL MISSING
 -COMMENT 8 NOT FULLY ADDRESSED. SHOW RELEVANT UTILITIES
 CROSSED (INCLUDING FRANCHISE UTILITIES)
 -COMMENT 15 NOT FULLY ADDRESSED, CCTV APPEARS TO SHOW
 EXISTING LATERAL ON SITE.
  