| 2023-04-13 11:38:49 | -PLEASE ADHERE TO DETAIL P-6 FOR PIGGING AND FLUSHING |
| | ASSEMBLY |
| | -PLEASE SUPPLY WATER AND SEWER DEMAND TABLE FOR |
| | EXISTING AND PROPOSED CONDITIONS |
| | -DENOTE THAT PROJECT FALLS WITHIN LIFT STATION 23 |
| | BOUNDARIES |
| | -SCALE PLAN VIEW SO THAT IT CAN BE PRINTED TO SCALE ON |
| | 11X17 |
| | -VERIFY EXISTING HYDRANT HAS ANCHOR TEE INSTALLED, ADD |
| | ONE IF NOT |
| | -CROSSING INFORMATION NEEDED AT ALL LOCATIONS WHERE |
| | PROPOSED WORK WILL BE IN CONFLICT WITH EXISTING |
| | UTILITIES |
| | -SHOW AND LABEL ALL EXISTING AND PROPOSED UTILITY |
| | EASEMENTS |
| | -PROVIDE PROFILES FOR PROPOSED WATER AND SEWER LINES UP |
| | TO R/W LINE |
| | -PROVIDE AN ERP FOR THE 36" WM ON THE EAST SIDE OF THE |
| | PROPERTY |
| | -VERIFY LOCATION OF EXISTING SANITARY MANHOLE WITH |
| | PROPOSED CONNECTION (IF MANHOLE EXISTS, IT WILL REQUIRE |
| | REHABBING. IF NO MANHOLE EXISTS IN LOCATION SHOWN ON |
| | PLANS, A DOGHOUSE MANHOLE WILL NEED TO BE PROPOSED. |
| | -PROVIDE CCTV OF EXISTING SEWER LINE BETWEEN THE |
| | NEAREST OFFSITE MANHOLE TO THE NORTH AND SOUTH OF THE |
| | PROJECT LOCATION. |
| | -CALL OUT ALL VALVES AND APPURTENANCES FOR EXISTING AND |
| | PROPOSED UTILITIES |
| | -8" CLEANOUT REQUIRED FOR 8" SANITARY SEWER LATERALS |
| | -SOURCE SAMPLE POINT REQUIRED FOR DOMESTIC LINE PER P-6 |
| | -EXISTING SEWER LATERAL NOT SHOWN, IT WILL NEED TO BE |
| | CUT AND CAP AT THE MAIN. |
| | -ADD LEGEND TO UTILITY PLAN |
| | -SPECIFY THE WORK BEING PROPOSED TO THE EXISTING 12" |
| | WATER MAIN |
| | -CALL OUT PIPE SIZE AND MATERIAL FOR ALL EXISTING AND |
| | PROPOSED UTILITIES |
| |