| 2023-04-06 10:35:42 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE |
| | PROVIDED AND MAY NEED FURTHER CLARIFICATIONS WHERE |
| | APPLICABLE. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, |
| | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, |
| | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE |
| | OCCUPANCIES (PARKING STRUCTURES) |
| | |
| | 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA |
| | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS |
| | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE |
| | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE |
| | BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED |
| | TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE |
| | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | IT IS RECOMMENDED FOR HIGH RISES HAVE TWO SEPARATE FDC |
| | LOCATIONS REMOTELY LOCATED TO SERVE THE STANDPIPE |
| | SYSTEM. |
| | |
| | 7A. PER NFPA 14 |
| | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| | NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE |
| | HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| | |
| | 7B. PER NFPA 1 |
| | 18.3 WATER SUPPLIES. |
| | |
| | 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING |
| | THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE |
| | PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, |
| | BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER |
| | CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE |
| | APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH |
| | SECTION 18.4. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE |
| | PRIMARY AND SECONDARY POWER SOURCES? |
| | |
| | 7C. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL |
| | MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE |
| | COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S |
| | ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S |
| | PLANNING AND ZONING OFFICE. |
| | |
| | 8. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS |
| | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, |
| | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 |
| | KEYWAY SYSTEM FOR BUILDING 6 OR MORE STORIES. |
| | |
| | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTERS |
| | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| | B44, SAFETY CODE FOR ELEVATORS. |
| | |
| | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| | IN THE HORIZONTAL POSITION. |
| | |
| | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | ALL NEW FIRE HYDRANTS AND FDCS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE |
| | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND |
| | FDCS SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET |
| | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER |
| | ARRIVING EMERGENCY VEHICLES. |
| | |
| | 12. EMERGENCY COMMUNCATION CENTER - COMMAND ROOM |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | |
| | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE |
| | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL |
| | BE APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER |
| | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 |
| | HOUR. |
| | |
| | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A |
| | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF |
| | 10 FT (3050 MM). |
| | |
| | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS |
| | (4) WORK TABLE. |
| | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION |
| | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |
| | AND NFPA 101 |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| | SYSTEMS. |
| | 24.9.1 GENERAL. |
| | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| | CAPABLE |
| | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| | FREQUENCIES |
| | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| | INSTALLED |
| | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| | AUTHORITY |
| | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| | DEGRADE |
| | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED |
| | FOR |
| | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| | SUCCESSFUL |
| | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| | FOR THE |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| | BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH |
| | FIRE DEPARTMENT. TESTING SHALL BE BY AN ACCEPTABLE |
| | NATIONAL STANDARD DOCUMENTING PERCENTAGES NOTED ABOVE |
| | AND BY ACTUAL RADIO TESTING BY FIRE PERSONNEL. IF THE |
| | MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL |
| | AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM |
| | 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, [email protected], |
| | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR |
| | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. |
| | |
| | |
| | 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, |
| | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA |
| | 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION |
| | EQUIPMENT, INCLUDING: |
| | |
| | THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED, |
| | INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH |
| | NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, |
| | STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY |
| | RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR |
| | RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY |
| | HAVING JURISDICTION. |
| | |
| | THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE |
| | INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE |
| | APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED |
| | MEANS OF INSPECTING, TESTING, AND MAINTAINING THE |
| | SYSTEM. |
| | |
| | ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL |
| | INSPECTOR IN ACCORDANCE WITH NFPA 101 SECTION 9.13. |
| | |
| | 16. AREAS OF REFUGE SHALL COMPLY WHERE APPLICABLE PER |
| | THE BUILDING CODE AND NFPA 101, CH 7, MEANS OF EGRESS. |
| | |
| | 17. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 18. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |