Plan Review Notes
Plan Review Notes For Project Z23030023
Project Number Z23030023
Review Stop PU
Sequence Number 1
Notes
Date Text
2023-05-11 11:49:52-LIST SIZE AND MATERIAL FOR ALL EXISTING AND PROPOSED
 UTILITIES
 -LABEL ALL EXISTING UTILITIES WITH IN THE PROJECT SCOPE
 -DENOTE CITY'S POINT OF SERVICE
 -PROVIDE A PROFILE FOR THE FIRE LINE FROM THE TAP TO
 THE CITY'S POINT OF SERVICE TO ENSURE PROPER CLEARANCES
 FOR UTILITY CONFLICTS
 -INCLUDE TOP/BOP ELEVATIONS FOR ALL UTILITY CONFLICTS
 -PROVIDE PROJECT ADDRESS AS WELL AS ADJACENT PARCELS
 -SHOW ALL UNDERGROUND DRY UTILITIES WITHIN THE PROJECT
 LIMITS
 -TRENCH RESTORATION NEEDED PER CITY DETAIL GC-8
 -DENOTE THE LIFT STATION BOUNDARY THAT THE PROJECT
 FALLS WITHIN
 - ENSURE GATE VALVE INSTALLATION WILL BE OUTSIDE OF
 SIDEWALK OR CURB AREAS
 -PRINT SHEETS SO THAT THEY ARE TO SCALE ON 11X17 PAPER
 - NEEDS TO BE DETERMINED IF EXISTING UTILITIES
 CURRENTLY HAVE DEDICATED UTILITY EASEMENTS
 -CORING INTO EXISTING MANHOLE WILL REQUIRE
 REHABILITATION
 - DENOTE SLOPE % AND DIRECTION FOR SANITARY SEWER
 -WHAT IS TO HAPPEN TO EXISTING SEWER UPON INSTALLATION
 OF THE NEW MANHOLE? (CITY RECORDS DO NOT SHOW AN
 EXISTING LATERAL OFF OF MAIN RUNNING TOWARDS EXISTING
 BUILDING)
 -CITY RECORDS DO NOT SHOW A WATER SERVICE BEING TAPPED
 OFF OF THE EXISTING 6" LINE. VERIFY THE EXISTENCE OF
 THE SERVICE LINE
 -IF EXISTING RUN IS ONLY SERVING HYDRANT, TAP OFF OF
 LINE IS NOT RECOMMENDED AS WATER IS TYPICALLY STAGNANT
 -FIRE HYDRANT CONNECTION MADE VIA ANCHOR TEE PER P-8
 -WHAT IS TO HAPPEN TO THE EXISTING FIRE HYDRANT?
 -USE OF A GATE VALVE AFTER THE 2" DOMESTIC CONNECTION,
 WITH A BALL VALVE FOR SAID CONNECTION, WOULD BE
 PREFERRED AS TO AVOID SERVICE INTERRUPTION DURING
 FUTURE MAINTENANCE/REPAIRS.
 -ON-SITE FDEP PERMIT WILL BE REQUIRED
 -SUBMIT CALCULATIONS TO VALIDATE SIZING OF PROPOSED
 FIRELINE
 -GREASE TRAP LOCATION NEEDS FURTHER EVALUATION ON
 BEHALF OF SANITARY COLLECTIONS DEPARTMENT
  
  