| 2023-05-18 17:22:43 | GENERAL COMMENTS: |
| | |
| | APPROVAL WITH CONDITION A LETTER FROM THE PALM BEACH |
| | COUNTY - TRAFFIC DIVISION, STATING THAT THE PROPOSED |
| | PROJECT MEETS THE TRAFFIC PERFORMANCE STANDARDS (TPS) |
| | OF THE COUNTY IS REQUIRED PRIOR TO MOVING FORWARD TO |
| | THE PUBLIC HEARING STAGE IS PROVIDED. |
| | |
| | |
| | 1.) SATISFIED |
| | |
| | PLEASE ADDRESS THE FOLLOWING IN THE JUSTIFICATION |
| | STATEMENT: |
| | |
| | |
| | 1A) SATISFIED |
| | |
| | ADDRESS OF THE AFFECTED AREA (1401 BRANDYWINE RD. |
| | APPEARS TO BE THE ADDRESS OF THE SUBJECT PROPERTY - NOT |
| | 1901 VILLAGE BOULEVARD). |
| | |
| | |
| | 1 B) SATISFIED |
| | |
| | THE STORAGE SPACE CALCULATIONS ARE INACCURATE IN THE |
| | PROPERTY HISTORY SECTION. |
| | |
| | 2.) NOT SATISFIED |
| | |
| | A LETTER FROM THE PALM BEACH COUNTY - TRAFFIC DIVISION, |
| | STATING THAT THE PROPOSED PROJECT MEETS THE TRAFFIC |
| | PERFORMANCE STANDARDS (TPS) OF THE COUNTY IS REQUIRED |
| | PRIOR TO MOVING FORWARD TO THE PUBLIC HEARING STAGE. |
| | |
| | 3.) SATISFIED |
| | |
| | PROVIDE WRITTEN CONFIRMATION THAT THE PUBLIC UTILITIES |
| | DEPARTMENT HAS REVIEWED THE PROPOSAL FOR WATER, SEWAGE |
| | TREATMENT, STORM DRAINAGE AND GARBAGE COLLECTION |
| | SERVICES. THE LETTER PROVIDED IN THE APPLICATION IS |
| | OUTDATED AND WILL NOT SUFFICE. PLEASE CONTACT THE CITY |
| | OF WEST PALM BEACH ENGINEERING SERVICES DEPARTMENT |
| | (561-494-1040) ON HOW TO OBTAIN THE REQUIRED LETTER. |
| | |
| | 4.) SATISFIED |
| | |
| | PROVIDE WRITTEN LETTERS FROM ALL PUBLIC UTILITIES |
| | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH |
| | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE |
| | PROVISIONS OF THEIR SERVICES: AT&T, FPU, FPL AND |
| | COMCAST. THE LETTERS PROVIDED IN THE APPLICATION IS |
| | OUTDATED AND WILL NOT SUFFICE. |
| | |
| | |
| | SITE PLAN COMMENTS: |
| | |
| | 1.) SATISFIED |
| | |
| | IT SHOULD BE NOTED IN THE SITE PLAN WHICH BUILDINGS ARE |
| | EXISTING, PROPOSED FOR DEMO AND RE-BUILT TO THE SAME |
| | FOOTPRINT AND PROPOSED NEW FOR CLARITY WITH THE |
| | SCOPE/DESCRIPTION OF WORK. |
| | |
| | 2.) SATISFIED |
| | |
| | PROVIDE THE BUILDING SETBACK FROM PROPOSED BUILDING #3 |
| | TO THE PROPERTY LINE TO DEMONSTRATE COMPLIANCE WITH THE |
| | SETBACK REQUIREMENTS OF THE ZLDRS. THE PROPERTY LINE |
| | SHALL BE MEASURED AS THE SHORTEST DISTANCE FROM THE |
| | FACE OF THE BUILDING TO THE PROPERTY LINE. |
| | |
| | 3.) SATFISFIED |
| | |
| | WHAT IS THE BUILDING SEPARATION BETWEEN THE EXISTING |
| | COVERED WASHING STATION (CANOPY) AND PROPOSED BUILDING |
| | #3? PLEASE PROVIDE THE DIMENSION FOR THE BUILDING |
| | SEPARATION IN THE PLAN. THE BUILDING SEPARATION MUST BE |
| | A MINIMUM OF 15 FT. [ZLDR S.94-202] |
| | |
| | 4.) SATISFIED |
| | |
| | PLEASE ADDRESS THE FOLLOWING IN THE SITE DATA TABULAR: |
| | |
| | |
| | 4A) SATISFIED |
| | |
| | THE PROPOSED BUILDING HEIGHT IS NOTED AS 30 FT., |
| | HOWEVER, THE BUILDING HEIGHT OF THE TALLEST PROPOSED |
| | STRUCTURE APPEARS TO BE CLOSER TO 16 FT. |
| | |
| | |
| | 4B) SATISFIED |
| | |
| | CLARIFICATION IS NEEDED ON THE 110.5 SQ. FT. |
| | PREFABRICATED STORAGE BUILDING ATTACHED TO PROPOSED |
| | BUILDING #3 (AS NOTED IN THE ARCHITECTURAL PLANS). IF |
| | THE INTENT IS TO PROVIDE THIS PREFAB BUILDING, THE |
| | ADDITIONAL STORAGE SQUARE FOOTAGE MUST BE ACCOUNTED |
| | FOR. |
| | |
| | 5.) SATISFIED |
| | |
| | THE PROPOSED BUILDING HEIGHT IN THE SITE DATA TABULAR |
| | IS NOTED AS 30 FT.; HOWEVER, THE PROPOSED BUILDING |
| | HEIGHT (ACCORDING TO THE ARCHITECTURAL DRAWINGS) APPEAR |
| | TO BE CLOSER TO 16 FT. PLEASE ADDRESS FOR CONSISTENCY. |
| | |
| | 6.) SATISFIED |
| | |
| | ALL PROPOSED STRUCTURES (I.E. LIGHT POLE FIXTURES, |
| | ETC.) MUST BE SHOWN IN THE PLANS AT THIS TIME TO |
| | DETERMINE IF THE LOCATION/PLACEMENT OF ANY STRUCTURES |
| | CONFLICT WITH UTILITIES LANDSCAPING, ETC. |
| | |
| | |
| | ARCHITECTURAL PLAN COMMENTS: |
| | |
| | 1.) SATISFIED |
| | |
| | AN "EXISTING PREFAB CHEMICAL STORAGE UNIT" IS SHOWN |
| | ATTACHED TO PROPOSED BUILDING #3 ON THE SOUTH SIDE OF |
| | THE BUILDING; HOWEVER, THIS IS STORAGE UNIT IS NOT |
| | REFLECTED IN THE SQUARE FOOTAGE CALCULATIONS, THE SITE |
| | PLAN, LANDSCAPE PLAN, CIVIL PLAN OR SURVEY. PLEASE |
| | ADDRESS FOR CONSISTENCY. |
| | |
| | 2.) SATISFIED |
| | |
| | LABELED ELEVATIONS FOR BUILDING #3 (CHEMICAL STORAGE |
| | BUILDING) APPEAR TO BE INCORRECT. PLEASE REVIEW SHEETS |
| | A1.2 AND A5.2 AND ADDRESS FOR CONSISTENCY. |
| | |
| | 3.) SATISFIED |
| | |
| | LABELED ELEVATIONS FOR BUILDING #1 (MAINTENANCE |
| | BUILDING) APPEAR TO BE INCORRECT. PLEASE REVIEW SHEETS |
| | A1.1 AND A5.1 AND ADDRESS FOR CONSISTENCY. |
| | |
| | |
| | LANDSCAPE PLAN COMMENTS: |
| | |
| | 1.) SATISFIED |
| | |
| | THE BUILDING SQUARE FOOTAGE BREAKDOWN ON SHEET LP.1 IS |
| | INCONSISTENT WITH THE INFORMATION PROVIDED ON SHEET |
| | SP.1. PLEASE ADDRESS FOR CONSISTENCY. |
| | |
| | 2.) SATISFIED |
| | |
| | THE FLOATING NOTE "PROPOSED WASH DOWN STATION" NEEDS TO |
| | BE REMOVED ON SHEET LP.1. THIS NOTE IS FROM THE |
| | PREVIOUS (EXPIRED) APPROVAL (REFERENCE: PB 770F), WHICH |
| | IS NO LONGER APPLICABLE TO THIS APPLICATION. |
| | |
| | |
| | INSTRUCTIONS FOR RESUBMITTAL: |
| | |
| | * PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN |
| | FORMAT. |
| | |
| | * WHEN REVISING ANY PLAN SHEETS, PLEASE MAKE SURE ANY |
| | CHANGES ARE REFLECTED IN ALL PLAN SETS. |
| | |
| | * WHEN REVISING ANY PLAN SHEETS/SETS, PLEASE BE SURE TO |
| | PROVIDE THE REVISION DATE. |
| | |
| | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR |
| | (4) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X |
| | 17 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS AND |
| | DOCUMENTS. |
| | |
| | * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY |
| | RESULT IN ADDITIONAL COMMENTS. |
| | |
| | * YOU WILL BE PERMITTED ONE (1) RESUBMITTAL AT NO |
| | ADDITIONAL COST. IF PREVIOUSLY-ISSUED COMMENTS CONTINUE |
| | TO NOT BE SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE |
| | ASSESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20 PERCENT |
| | OF THE ORIGINAL APPLICATION FEE. |
| | |
| | ALEXIS SANGELEER |
| | PLANNER |
| | [email protected] |
| | 561-822-1443 |
| |