Plan Review Notes
Plan Review Notes For Project Z23020027
Project Number Z23020027
Review Stop STORM
Sequence Number 1
Notes
Date Text
2023-03-08 09:45:12THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. SURVEY IDENTIFIES THE SITE WITHIN A SPECIAL FLOOD
 HAZARD AREA (SFHA) WITH A BASE FLOOD ELEVATION OF 14 FT
 NAVD1988. STRUCTURES WITHIN A SFHA ARE TO HAVE A
 MINIMUM OF 2 FEET OF FREEBOARD ABOVE THE BASE FLOOD
 ELEVATION.
  
 2. CONFIRM NPBCID APPROVES THE DEPTH OF THE OUTFALL
 INTO THE LAKE SYSTEM. THE PROVIDED DETAIL DRAWING NO.
 N-003 SHOWS THE TOP OF THE PIPE IS TO BE 2 FEET BELOW
 THE CONTROL ELEVATION OF THE LAKE.
  
 3. COMPLETE THE SCALE BAR ON SHEET C-201.
  
 4. ADA STRIPING DETAIL SHOULD MATCH CITY LAND
 DEVELOPMENT CODE SECTION 94-485.
  
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION.
  
 3. PROVIDE COPY OF NPBCID PERMIT BEFORE START OF
 CONSTRUCTION.
  
 4. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  
  