2023-05-15 16:22:47PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -FDC TO THE NORTHEAST APPEARS TO BE INSTALLED
 INCORRECTLY. IT IS INSTALLED UPSTREAM OF THE FIRELINE
 BACKFLOW ASSEMBLY, WHEREAS USUALLY IT IS INSTALLED
 DOWNSTREAM.
 -IN PRIOR RESPONSE LETTER, FOR: VERIFY PRIVATE FIRE
 SYSTEM WILL NOT HAVE ANY ADDED CHEMICALS OR AUXILIARY
 WATER SOURCES SUCH AS WELLS OR TANKS, RECEIVED THE
 FOLLOWING RESPONSE: COMMENT NOTED. RESPONSE WAS
 INSUFFICIENT. NEED CONFIRMATION IF PRIVATE FIRE SYSTEM
 WILL HAVE ANY ADDED CHEMICALS OR AUXILIARY WATER
 SOURCES SUCH AS WELLS OR TANKS. IF NOT, DCDA TYPE IS
 FINE.
 -PROPERTY OWNER WOULD BE REQUIRED TO RECORD BACKFLOW
 COVENANT AS A CONDITION OF WATER SERVICE.
 -FIRELINE BACKFLOW ASSEMBLY INSTALLATION INSIDE
 BUILDING AND ASSOCIATED PIPING AND COMPONENTS UPSTREAM
 OF IT MUST COMPLY WITH ALL WPB PUBLIC UTILITIES AND
 ENGINEERING DEPARTMENTS REQUIREMENTS. ALL PIPING
 UPSTREAM OF FIRELINE BACKFLOW ASSEMBLY NEED BE DUCTILE
 IRON PIPE, AND INSTALLATION MUST MEET REQUIREMENTS OF
 WATER SERVICE STANDARD DETAIL WS5. PLEASE NOTIFY FIRE
 SYSTEM DESIGNER OF THIS REVIEW COMMENT NOW DURING PPRC
 AND WILL REVIEW FURTHER AT ENGINEERING DEVELOPMENT
 SUBMITTAL.
 RESPECTFULLY,
 MARK HURLEY [email protected]