2023-03-03 10:44:43PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SURVEYS SHOW VARIOUS EXISTING EASEMENTS ON THE
 PROPERTY INCLUDING A WATER AND SEWER UTILITY EASEMENT.
 WHAT IS HAPPENING TO THE EASEMENTS, AND ARE THERE
 CURRENTLY ANY WATER AND SEWER UTILITIES IN THE FIVE
 FOOT WATER AND SEWER EASEMENT?
 -COOLING TOWERS CANNOT BE FED FROM FIRELINES.
 -A1.7, A1.8, A4.1, AND Z7.0 SHOW WATER TANKS. WHAT ARE
 THEY USED FOR AND WILL THEY BE CONNECTED TO ANY OF THE
 PLUMBING OR FIRE SYSTEMS?
 -SHOW AND LABEL ALL EXISTING AND PROPOSED EASEMENTS ON
 CIVIL ENGINEERING PLANS.
 -SHOW AND LABEL WATER METERS AND BACKFLOW ASSEMBLIES ON
 CIVIL ENGINEERING PLANS.
 -DOMESTIC WATER METERS TO BE INSTALLED ABOVE-GROUND,
 OUTSIDE OF BUILDING, AND ADJACENT PROPERTY LINE.
 -LABEL DOMESTIC BACKFLOW ASSEMBLIES WITH RP TYPE AND
 SIZE.
 -WILL DOMESTIC METER BE USED FOR IRRIGATION? IF NOT, IS
 SEPARATE METERED IRRIGATION WATER SERVICE NEEDED?
 -SHOW AND LABEL GREASE TRAPS AND TRANSFORMERS ON
 ENGINEERING PLANS IF THEY WILL BE OUTSIDE OF BUILDING.
 -SHOW AND LABEL FDC IF THEY ARE NEEDED OR REQUIRED.
 ENSURE THEY ACCEPTABLE DISTANCE TO FIRE HYDRANTS.
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SOURCES SUCH AS WELLS OR
 TANKS.
 -WATER METERS 8 INCHES AND LARGER ARE NOT STOCKED AND
 HAVE TO BE ORDERED AFTER UTILITY QUOTE IS PAID. LEAD
 TIMES MAY BE OVER 6 MONTHS FROM TIME OF PAYMENT.
 -WATER METERS 6 INCH OR LARGER NEED TO BE ACCESSIBLE
 AND REPLACEABLE BY FORD F350 CRANE TRUCK.
 -SHOW UTILITIES FROM ENGINEERING PLAN ON LANDSCAPING
 PLAN AND ENSURE NO CONFLICTS BETWEEN UTILITIES AND
 LANDSCAPING.
 -NORTHEAST FIRELINE IS EXCESSIVELY LONG. BACKFLOW
 ASSEMBLY SHOULD BE CLOSER TO TAP THAN BUILDING. ALSO
 ENSURE FIRELINE IS ON PROPERTY LINE AND NOT IN NORTH
 RIGHT OF WAY.
 -SHOW EXISTING METERED WATER SERVICES ON DEMO PLAN.
 -ALL INSTALLED CONTAINMENT BACKFLOW ASSEMBLIES MUST BE
 LEAD-FREE AND USC-APPROVED (BY SIZE, MAKE, MODEL,
 ORIENTATION, VALVING, AND BYPASS).
 -MANY OF THE SURROUNDING STREETS WILL NEED PAVEMENT
 RESTORATION DUE TO UTILITY WORK.
 -C10 HAS DUPLICATE STANDARD DETAILS. PLEASE ELIMINATE
 THE DUPLICATE.
 -ADD WATER SERVICES STANDARD DETAILS WS2, WS5, WS7 TO
 ENGINEERING PLAN SET.
 -EXISTING FIRE HYDRANT ACROSS FROM BROWARD AVE APPEARS
 TO BE IN MIDDLE OF PROPOSED WALKWAY.
 -SHOW AND LABEL WHAT IS HAPPENING TO EXISTING UTILITY
 POLES AT SOUTH SIDE OF PROPERTY.
 -EXISTING WATER MAIN LAYOUT SHOWN ON PONCE DE LEON
 SHOWN ON C5 MAY NOT BE ACCURATE. REFERENCE WATER DESIGN
 RECORDS FROM 312 23RD ST.
  