| 2023-03-08 18:45:49 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE |
| | RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD |
| | ZONE AE, WITH A BASE FLOOD ELEVATION OF 6 FT NAVD. THE |
| | FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED |
| | MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL |
| | BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD |
| | ELEVATION. |
| | |
| | 3. ACCESSIBLE ROUTE FROM SIDEWALK. SITE PLAN, SHEET |
| | AS-1.0, DOES NOT SHOW A PEDESTRIAN/WHEELCHAIR |
| | ACCESSIBLE ROUTE FROM THE SIDEWALK TO THE TWO LOBBY |
| | ENTRANCES THAT DOES NOT REQUIRE THE PERSON TO TRAVEL |
| | ALONG THE VEHICULAR TRAVEL LANE. WHEN SUBMITTED FOR |
| | PERMIT, THE PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE |
| | ROUTE, COMPLYING WITH SECTIONS 206.2 AND 402.2 OF |
| | FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC |
| | RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY |
| | ENTRANCES. |
| | |
| | 4. ACCESSIBLE ROUTE BETWEEN TOWER LOBBIES. SITE PLAN, |
| | SHEET AS-1.0, DOES NOT SHOW A PEDESTRIAN/WHEELCHAIR |
| | ACCESSIBLE ROUTE BETWEEN THE TWO LOBBY ENTRANCES THAT |
| | DOES NOT REQUIRE THE PERSON TO TRAVEL ALONG THE |
| | VEHICULAR TRAVEL LANE. WHEN SUBMITTED FOR PERMIT, THE |
| | PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE, |
| | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA |
| | ACCESSIBILITY CODE, CONNECTING ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS WITHIN THE BUILDING OR FACILITY |
| | |
| | 5. VAN ACCESSIBLE PARKING SPACES. SITE PLAN, SHEET |
| | AS-1.0, SHOWS 8 ACCESSIBLE PARKING SPACES BUT NONE ARE |
| | DESIGNATED AS VAN ACCESSIBLE. 2 OF THE 8 SHOULD BE |
| | LABELED AS VAN ACCESSIBLE. PER SECTION 208.2.4 OF |
| | FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX REQUIRED |
| | ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ???VAN ACCESSIBLE??? AND DESIGNED |
| | IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 6. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC |
| | VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1 |
| | IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE |
| | REQUIREMENTS. |
| | |
| | 7. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 9. GREASE INTERCEPTOR. A GREASE INTERCEPTOR MAY BE |
| | REQUIRED FOR THE PROPOSED CAFE. FOR INFORMATION ON THE |
| | REQUIRED TYPE, SIZE AND LOCATION, PLEASE CONTACT RYAN |
| | BROWN, CHIEF PLUMBING INSPECTOR, DEVELOPMENT SERVICES |
| | DEPARTMENT, AT (561) 805-6692, OR BY EMAIL: |
| | [email protected] |
| | |
| | 10. AMENITIES LEVEL, ELEVATOR LOBBY DOORS MAY HAVE TO |
| | BE MOVED SO THAT THE DOORS SWING OPEN IN THE DIRECTION |
| | OF EGRESS, TOWARD THE STAIRS. SHEET A-1.2 CURRENTLY |
| | SHOWS THE DOORS VERY CLOSE TO THE STAIR EXIT DOOR, SUCH |
| | THAT REVERSING THE SWING DIECTION AS REQUIRED BY |
| | SECTION 1010.1.2 OF FLORIDA BUILDING CODE, MAY REQUIRE |
| | MOVING THE ELEVATOR LOBBY DOORS. |
| | |
| | 11. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 12. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND |
| | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF |
| | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL |
| | NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A |
| | CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES |
| | DEPARTMENT. |
| | |
| | 13. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER |
| | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, |
| | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE |
| | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF |
| | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION |
| | THAT MAY AFFECT THE USE OF THEIR PROPERTY. |
| | |
| | 14. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION |
| | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, |
| | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT |
| | (561) 805 6659, OR BY EMAIL: [email protected] |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |