2023-03-08 18:45:49DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE, WITH A BASE FLOOD ELEVATION OF 6 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 3. ACCESSIBLE ROUTE FROM SIDEWALK. SITE PLAN, SHEET
 AS-1.0, DOES NOT SHOW A PEDESTRIAN/WHEELCHAIR
 ACCESSIBLE ROUTE FROM THE SIDEWALK TO THE TWO LOBBY
 ENTRANCES THAT DOES NOT REQUIRE THE PERSON TO TRAVEL
 ALONG THE VEHICULAR TRAVEL LANE. WHEN SUBMITTED FOR
 PERMIT, THE PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE
 ROUTE, COMPLYING WITH SECTIONS 206.2 AND 402.2 OF
 FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC
 RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES.
  
 4. ACCESSIBLE ROUTE BETWEEN TOWER LOBBIES. SITE PLAN,
 SHEET AS-1.0, DOES NOT SHOW A PEDESTRIAN/WHEELCHAIR
 ACCESSIBLE ROUTE BETWEEN THE TWO LOBBY ENTRANCES THAT
 DOES NOT REQUIRE THE PERSON TO TRAVEL ALONG THE
 VEHICULAR TRAVEL LANE. WHEN SUBMITTED FOR PERMIT, THE
 PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE,
 COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA
 ACCESSIBILITY CODE, CONNECTING ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY
  
 5. VAN ACCESSIBLE PARKING SPACES. SITE PLAN, SHEET
 AS-1.0, SHOWS 8 ACCESSIBLE PARKING SPACES BUT NONE ARE
 DESIGNATED AS VAN ACCESSIBLE. 2 OF THE 8 SHOULD BE
 LABELED AS VAN ACCESSIBLE. PER SECTION 208.2.4 OF
 FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX REQUIRED
 ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ???VAN ACCESSIBLE??? AND DESIGNED
 IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICULAR ACCESS ROUTE)
  
 6. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC
 VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1
 IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE
 REQUIREMENTS.
  
 7. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 9. GREASE INTERCEPTOR. A GREASE INTERCEPTOR MAY BE
 REQUIRED FOR THE PROPOSED CAFE. FOR INFORMATION ON THE
 REQUIRED TYPE, SIZE AND LOCATION, PLEASE CONTACT RYAN
 BROWN, CHIEF PLUMBING INSPECTOR, DEVELOPMENT SERVICES
 DEPARTMENT, AT (561) 805-6692, OR BY EMAIL:
 [email protected]
  
 10. AMENITIES LEVEL, ELEVATOR LOBBY DOORS MAY HAVE TO
 BE MOVED SO THAT THE DOORS SWING OPEN IN THE DIRECTION
 OF EGRESS, TOWARD THE STAIRS. SHEET A-1.2 CURRENTLY
 SHOWS THE DOORS VERY CLOSE TO THE STAIR EXIT DOOR, SUCH
 THAT REVERSING THE SWING DIECTION AS REQUIRED BY
 SECTION 1010.1.2 OF FLORIDA BUILDING CODE, MAY REQUIRE
 MOVING THE ELEVATOR LOBBY DOORS.
  
 11. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 12. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A
 CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES
 DEPARTMENT.
  
 13. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 14. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  