2023-03-06 15:49:53PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SHOW ALL EXISTING WATER METERS, WATER METER BOXES,
 BACKFLOW ASSEMBLIES, AND WATER SERVICES ON ENGINEERING
 PLANS AND LABEL WHAT IS HAPPENING TO THEM.
 -SHOW AND LABEL ALL PROPOSED WATER METERS AND BACKFLOW
 ASSEMBLIES.
 -ENSURE THAT EXISTING AND PROPOSED WATER METERS AND
 BACKFLOW ASSEMBLIES WILL NOT BE RUN OVER BY VEHICLES.
 -ENSURE THAT EXISTING AND PROPOSED WATER METER BOXES
 WILL NOT BE IN ASPHALT OR CURBS.
 -SHOW AND LABEL EXISTING WATER SERVICE LINES FEEDING
 THE WATER METERS NEAR THE SOUTHWEST CORNER OF 2 STORY
 BUILDING.
 -SHOW ALL EXISTING AND PROPOSED SANITARY SEWER LATERALS
 AND CLEANOUTS.
 -SHOW AND LABEL ANY EXISTING UTILITY EASEMENTS.
 -LABEL PROPOSED DOMESTIC BACKFLOW ASSEMBLIES WITH RP
 TYPE AND SIZE.
 -POLES AND STRUCTURES MINIMUM 3 FEET AWAY FROM WATER
 METER BOXES.
 RESPECTFULLY,
 MARK HURLEY [email protected]