2023-04-11 17:37:38THESE COMMENTS ARE FROM THE REVIEW OF THE 3-22-2023
 SUBMITTAL AND CAN BE ADDRESSED WITH THE ENGINEERING
 PERMIT SUBMTITAL:
  
 1. FOR THE WEIR DETAIL ON SHEET C-9, REVERSE THE FLOW
 ARROWS BECAUSE THE WEIR WILL BE OVER THE OUTLET PIPE IN
 STRUCTURE D-01.
  
 2. THE DRAINAGE INLETS WITH TWO OF MORE CONNECTIONS TO
 EXFILTRATION TRENCHES WILL NEED TO BE LARGE ENOUGH TO
 FIT PRB'S OVER EACH EXFILTRATION TRENCH CONNECTION.
  
 3. UPDATE REFERENCES TO FDOT STANDARD INDEX NUMBERS TO
 FDOT STANDARD PLAN NUMBERS.
  