| Plan Review Notes For Project Z22120034 |
| Project Number |
Z22120034 |
|
| Review Stop |
L |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-06 16:33:13 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: GRACE FELLOWSHIP Z22120034 | | | FEBRUARY 6, 2023 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. THE DRAINAGE STRUCTURES TO THE WEST OF THE NEW | | | BUILDING SHOWN ON THE CIVIL PLANS ARE NOT SHOWN ON THE | | | LANDSCAPE PLAN. STRUCTURE D-01 AND D-02 APPEAR TO | | | CONFLICT WITH EXISTING TREES. | | | | | | 2. SHOW HEDGE SCREENING FOR ABOVE GROUND UTILITIES | | | NORTHEAST OF THE NEW BUILDING AND EAST SIDE OF THE | | | BUILDING PER THE CIVIL PLANS. | | | | | | 3. THERE ARE MULTIPLE UTILITIES SHOWN ON THE CIVIL | | | PLANS THAT ARE NOT SHOWN ON THE LANDSCAPE PLANS AND | | | THERE ARE CONFLICTS WITH REQUIRED LANDSCAPING. | | | ??? THE FIRE HYDRANT CANNOT BE PLACED IN THE TERMINAL | | | LANDSCAPE ISLAND IN CONFLICT WITH REQUIRED TREES. MOVE | | | TO THE OTHER SIDE OF THE DRIVE WHERE THERE IS ADEQUATE | | | ROOM. | | | ??? SOUTHEAST CORNER OF THE NEW PARKING AREA SHOWS A | | | UTILITY STRUCTURE THAT WILL CONFLICT WITH EXISTING PALM | | | AND TREE. | | | ??? EXISTING GREASE TRAP AND 6??? FIRE SERVICE ARE NOT | | | SHOWN ON LANDSCAPE PLAN AND ARE IN CONFLICT WITH | | | PROPOSED TREES. | | | |
| |