Plan Review Notes
Plan Review Notes For Project Z22120027
Project Number Z22120027
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2023-01-06 11:58:50PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -DO 309 AND 313 CLEMATIS CURRENTLY HAVE GREASE TRAPS?
 -ARE THE EXISTING WATER AND SEWER SERVICES SUFFICIENT
 FOR ANY INCREASED DEMAND?
 -BOTH PROPERTIES HAVE EXISTING FIRELINE WATER SERVICES.
 THE FIRELINE BACKFLOW ASSEMBLY AT 313 CLEMATIS IS
 DAMAGED AND NEEDS REPAIR IN ORDER TO USE IT.
 -THE WATER SERVICES FOR 313 CLEMATIS DO NOT HAVE ACTIVE
 USAGE BILLING ACCOUNTS SETUP YET WITH UTILITY BILLING
 IN ORDER TO USE THEM.
 -ALL BACKFLOW ASSEMBLIES ARE OUT OF COMPLIANCE FOR
 BACKFLOW TESTING.
 -VERIFY IF FIRE SYSTEMS WILL HAVE ANY ADDED CHEMICALS
 OR ANY AUXILIARY WATER SOURCES SUCH AS WELLS.
 -COULD NOT FIND CIVIL ENGINEERING PLAN IN SUBMITTAL
 PACKAGE. ADD IF MAKING ANY CHANGES TO WATER OR SEWER
 SERVICES.
 RESPECTFULLY,
 MARK HURLEY [email protected]