| 2023-03-10 09:07:14 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 2-23-2023 SUBMTITAL: | | | | | | 1.[NOT SATISFIED] TWO SCALES LISTED ON SHEET S-2. THE | | | SCALE BAR BY THE NORTH ARROW ON THE LEFT BOTTOM SIDE OF | | | THE PAGE LISTS THE SCALE AS 1 INCH EQUALS 50 FEET. THE | | | SCALE BY THE NORTH ARROW ON THE BOTTOM RIGHT OF THE | | | PAGE LISTS THE SCALE AS 1 INCH EQUALS 100 FEET. | | | | | | 2. [NOT SATISFIED] ADVISE IF A FDEP PERMIT WILL BE | | | NEEDED. THE SUBMITTED PERMIT EXPIRED 10/12/2013 AND WAS | | | FOR A DIFFERENT DOCK LAYOUT. PRIOR TO CONSTRUCTION | | | PROVIDE A VALID FDEP PERMIT FOR WORK WITHIN WATERS OF | | | THE STATE. | | | | | | 3. [NOT SATISFIED] SHOW ON SHEETS S-2 AND S-3 THE | | | 18-INCH RCP DRAINAGE PIPE FROM THE INLET IN N. FLAGLER | | | DRIVE TO THE SEAWALL. THE PIPE IS SHOWN ON THE SURVEY. | | | | | | 4. [NOT SATISFIED] SHOW ON SHEET S-3 THE 5 FT STORM | | | DRAINAGE EASEMENT SHOWN ON THE SURVEY. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
| |