Plan Review Notes
Plan Review Notes For Project Z22120020
Project Number Z22120020
Review Stop PU-CS
Sequence Number 2
Notes
Date Text
2023-02-24 11:38:24PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -FIRE HYDRANT, FIRELINE BACKFLOW ASSEMBLY, AND FDC ARE
 PROPOSED TO BE LOCATED IN 12 FOOT BICYCLE PATH
 EASEMENT. PLEASE VERIFY THAT IS ACCEPTABLE AND WILL NOT
 CONFLICT WITH ANY EASEMENT STIPULATIONS.
 -FIRE HYDRANT AND SOME PORTIONS OF FIRELINE ARE IN THE
 20 FOOT EASEMENT. PLEASE PROVIDE MORE INFORMATION ABOUT
 THE EASEMENT INCLUDING WHAT TYPE IT IS AND WHAT IT IS
 USED FOR. ALSO VERIFY THE FIRE COMPONENTS DO NOT
 CONFLICT WITH ANY EASEMENT STIPULATIONS.
 -AT ENGINEERING DEVELOPMENT SUBMITTAL: ADDITIONAL
 EASEMENTS MAY BE REQUIRED; ENGINEERING PLAN DESIGN MAY
 NEED REVISION.
 -FIRELINE BACKFLOW ASSEMBLY NEEDS TO BE RPDA TYPE,
 LEAD-FREE, AND USC APPROVED. ENSURE FIRE PLAN DESIGNERS
 ARE AWARE OF THE REQUIREMENTS.
 RESPECTFULLY,