Plan Review Notes
Plan Review Notes For Project Z22120020
Project Number Z22120020
Review Stop PU
Sequence Number 2
Notes
Date Text
2023-03-09 15:53:57-PLEASE PROVIDE A PROFILE OF THE PROPOSED 6" WATER MAIN
 -SHOW ALL DRY UTILITIES WITHIN THE SCOPE OF WORK
 -ANCHOR TEES ARE A REQUIREMENT FOR FIRE HYDRANT
 INSTALLATION PER CITY STANDARDS, PLEASE INCORPORATE
 THIS INTO YOUR DESIGN
 -DENOTE THE POINT OF SERVICE FOR THE PROPOSED FIRE LINE
  