Plan Review Notes
Plan Review Notes For Project Z22120020
Project Number Z22120020
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2023-02-24 10:00:07Z22120020 ??? 1525 N FLAGLER DOCK, RESUBMITTAL
  
 COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENGINEERING SERVICES AT 561-494-1098 [email protected]
 PLEASE PROVIDE CIVIL PLANS SHOWING WATER CONNECTIONS,
 INCLUDING POTABLE. PROVIDE CALCULATIONS ON PLANS OF
 EXISTING AND PROPOSED DEMANDS FOR WATER & SEWER
 (AVERAGE, MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS.
 CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER (IF ANY)
 AND PER FAC 64-E.008 FOR WATER.
  
 PLEASE OBTAIN AND PROVIDE A COPY OF APPROVED FDEP ERP
 SELF-CERTIFICATION FORM AS CONDITION OF APPROVAL. HTTPS
 ://FLORIDADEP.GOV/WATER/SUBMERGED-LANDS-ENVIRONMENTAL-R
 ESOURCES-COORDINATION/CONTENT/ERP-E-PERMITTING
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 FORMAL ENGINEERING SUBMITTAL:
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
  