| 2023-02-24 10:00:07 | Z22120020 ??? 1525 N FLAGLER DOCK, RESUBMITTAL |
| | |
| | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, |
| | ENGINEERING SERVICES AT 561-494-1098 [email protected] |
| | PLEASE PROVIDE CIVIL PLANS SHOWING WATER CONNECTIONS, |
| | INCLUDING POTABLE. PROVIDE CALCULATIONS ON PLANS OF |
| | EXISTING AND PROPOSED DEMANDS FOR WATER & SEWER |
| | (AVERAGE, MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. |
| | CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER (IF ANY) |
| | AND PER FAC 64-E.008 FOR WATER. |
| | |
| | PLEASE OBTAIN AND PROVIDE A COPY OF APPROVED FDEP ERP |
| | SELF-CERTIFICATION FORM AS CONDITION OF APPROVAL. HTTPS |
| | ://FLORIDADEP.GOV/WATER/SUBMERGED-LANDS-ENVIRONMENTAL-R |
| | ESOURCES-COORDINATION/CONTENT/ERP-E-PERMITTING |
| | |
| | BACKFLOW ASSEMBLY AND METERS: |
| | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER |
| | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING |
| | TO THEM. |
| | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY |
| | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO |
| | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO |
| | STRUCTURES WITHIN EASEMENT. |
| | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION |
| | OF WATER METER AND BACKFLOW |
| | PREVENTION. |
| | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY |
| | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER |
| | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO |
| | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE |
| | INSTALLED ABOVE-GROUND ONLY. |
| | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE |
| | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. |
| | |
| | FORMAL ENGINEERING SUBMITTAL: |
| | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF |
| | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| | LEAD-FREE DESIGN. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES |
| | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY |
| | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT |
| | PARCELS. |
| | |
| | [email protected] |
| | |
| |