Plan Review Notes
Plan Review Notes For Project Z22120020
Project Number Z22120020
Review Stop STORM
Sequence Number 1
Notes
Date Text
2023-01-12 09:36:31THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. TWO SCALES LISTED ON SHEET S-2.
  
 2. ADVISE IF A FDEP PERMIT WILL BE NEEDED. THE
 SUBMITTED PERMIT EXPIRED 10/12/2013 AND WAS FOR A
 DIFFERENT DOCK LAYOUT.
  
 3. SHOW ON SHEETS S-2 AND S-3 THE 18??? RCP DRAINAGE
 PIPE FROM THE INLET IN N. FLAGLER DRIVE TO THE SEAWALL.
 THE PIPE IS SHOWN ON THE SURVEY.
  
 4. SHOW ON SHEET S-3 THE 5??? STORM DRAINAGE EASEMENT
 SHOWN ON THE SURVEY.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT