 TRAFFIC COMMENTS
 1) A METHODOLOGY MEETING SHOULD HAVE BEEN SCHEDULED.
 PLEASE DO SO.
 2) PROVIDE AN UPDATED TRAFFIC STUDY BASED ON MORE
 RECENT OR EXISTING COUNTS, AS THE 2018 COUNTS ARE
 OUTDATED, AS RECOMMENDED IN THE ANALYSIS AS WELL
 3) AN AERIAL SATELLITE MAP SHOWCASING PROPOSED
 DEVELOPMENT WITH RESPECT TO NEIGHBORING AREA SHOULD BE
 PROVIDED IN THE TRAFFIC STUDY
 4) SHOULD TABLE 1 THROUGH 3 MAIN CAPTIONS BE TOTAL
 MAXIMUM DRI OR MAXIMUM VESTED TRIP GENERATION?
 5) BELOW EACH TABLE PLEASE PROVIDE REFERENCES FOR EACH
 PARAMETER (I.E. RATE/EQUATION, INTERNALIZATION AND
 PASS-BY PERCENTAGES)
 6) PROVIDE TRIP GENERATION CALCULATION TABLE(S)
 SPECIFIC TO THE PROPOSED DEVELOPMENT (I.E. ONLY TRIPS
 GENERATED BY THE PROPOSED DEVELOPMENT). TABLE 7-9 SHOW
 AGGREGATE OF EXISTING/APPROVED AND CURRENTLY PROPOSED,
 MAIN CAPTION SHOULD BE CORRECTED ACCORDINGLY (E.G.
 APPROVED/BUILT PLUS PROPOSED DEVELOPMENTS)
 7) TABLE 10 NEEDS TO BE CORRECTED, AS VESTED
 DEVELOPMENT SHOULD REFER TO THE TOTAL MAXIMUM DRI,
 WHILE PROPOSED DEVELOPMENT SHOULD REFER TO
 EXISTING/APPROVED AND CURRENTLY PROPOSED. PLEASE
 CORRECT
 8) IN TABLE 10. DO DRIVEWAY TRIPS REFER TO TOTAL TRIPS
 MINUS INTERNALIZATION? (I.E. PASS-BY TRIPS ARE NOT
 DEDUCTED). IF SO, PLEASE INSERT A FOOTNOTE SPECIFYING
 THAT.
 9) SYNCHRO OUTPUTS AND LOS SUMMARY TABLES SHOULD
 INCLUDE THE FOLLOWING SCENARIOS: EXISTING, FUTURE
 NO-BUILD AND FUTURE BUILD XXX (INSERT BUILD-OUT YEAR
 AND APPLY GROWTH FACTORS ACCORDINGLY). RESULTS FOR EACH
 SCENARIO SHOULD BE SUMMARIZED AND COMPARED IN A TABLE.
 CURRENT SYNCHRO OUTPUTS INDICATE 2022 BUILD-OUT YEAR,
 IS THAT EXISTING OR AN OUTDATED BUILD-OUT ANALYSIS?
 10) PROVIDE MORE DETAILS PERTAINING THE CENTREPARK DRI
 EXTENT AND TRIP ALLOCATION. SPECIFICALLY: MAP
 SHOWCASING THE EXTENT OF THE DRI AND EACH OF THE SITES;
 A COMPREHENSIVE SPREADSHEET/TABLE SHOWCASING MAXIMUM
 ALLOWED SF/ROOMS/DU ALLOCATION FOR LAND-USE TYPE VERSUS
 EXISTING-BUILT, APPROVED-IN-CONSTRUCTION,
 PLANNED-PROPOSED DEVELOPMENTS AND LEFT OVER BALANCES,
 FOR EACH SITES AND OVERALL
 11) THE TPS LETTER WAS ISSUED WITH AN ANTICIPATED
 BUILD-OUT YEAR IN 2024, WHILE THE TRAFFIC STUDY ASSUMES
 BUILD-OUT IN 2026. PLEASE EXPLAIN AND, IF NEEDED,
 REVISE THE TRAFFIC STUDY OR PROVIDE AN UPDATED TPS
 LETTER
 12) PROVIDE EXPLANATION OR HISTORICAL REFERENCE WITH
 RESPECT TO THE CHANGE IN MAXIMUM PARCEL AND DRI OVERALL
 ALLOCATIONS, AS SHOWN IN EXHIBIT B. WHAT METHODOLOGY OR
 REASONING WAS APPLIED TO REDUCE/INCREASE ORIGINAL DRI
 ALLOCATIONS?
 13) THE ORIGINAL INTERNALIZATION CALCULATION TABLE IS
 DATED 2005. BECAUSE OF THE CHANGE IN OVERALL DRI
 ALLOCATION, LAND USE TYPE, AND THE USE OF THE LATEST
 ITE TRIP GENERATION RATES IN THE PROPOSED DEVELOPMENT
 TRAFFIC STUDY, IT WOULD BE LOGICAL AND NECESSARY TO
 RE-CALCULATE INTERNALIZATION PARAMETERS AND RATES BASED
 ON LATEST DRI ALLOCATION AND ITE/COUNTY RATES AND
 METHODOLOGY. PLEASE DO SO AND PROVIDE THE WORKING
 SPREADSHEET AS PART OF NEXT RESUBMISSION
 SITE COMMENTS
 14) PROVIDE A HORIZONTAL CONTROL SITE PLAN FOR THE
 GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED
 FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING
 STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES,
 CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY
 SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED
 AND DIMENSIONED
 15) IN THE HORIZONTAL CONTROL SITE PLAN, PLEASE
 SHOWCASE BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS,
 PAVEMENT MARKINGS, PARKING STALLS, ETC.) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT
 16) PROVIDE A SIGNAGE AND PAVEMENT MARKING PLAN.
 INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED
 DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. SUCH
 SITE PLAN CAN BE SEPARATE OR INTEGRATED IN THE
 HORIZONTAL CONTROL ONE
 17) ALL TRANSPORTATION RELATED ITEMS (I.E. PARKING
 STALL, DRIVE AISLES, RAMP) WITHIN THE GARAGE PLANS NEED
 TO BE PROPERLY LABELED AND DIMENSIONED (I.E. LENGTH,
 WIDTH, SLOPE PERCENTAGES)
 18) PER CITY CODE SEC94-111(C)(1): ???IN THOSE CASES
 WHERE THE SIDE OF ANY STALL IS ADJACENT TO A WALL,
 FENCE, BUILDING, OR OTHER PHYSICAL OBSTRUCTION, THE
 STALL WIDTHS SHALL BE INCREASED BY A MINIMUM OF ONE
 FOOT. WHERE THERE IS AN OBSTRUCTION ON BOTH SIDES OF
 THE STALL, THE STALL WIDTHS SHALL BE INCREASED BY A
 MINIMUM OF TWO FEET.??? PLEASE APPLY AND SHOWCASE SUCH
 REQUIREMENT IN THE GARAGE PLANS
 19) TURN-AROUND SPACES SHOULD BE PROVIDED, AND CLEARLY
 MARKED AS SUCH AT EACH DEAD-END(S) OF THE GARAGE.
 PLEASE REVISE THE SITE PLANS ACCORDINGLY.
 20) PROPOSED LOADING ZONE(S) ARE NOT CLEARLY DEPICTED
 NOR DIMENSIONED IN THE ARCHITECTURAL PLANS. PLEASE
 REVISE AND PROVIDE CODE REFERENCE TO MINIMUM REQUIRED
 AND PROVIDED DIMENSIONS.
 21) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL
 PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS
 22) PROVIDE ENGINEERING REFERENCE AND SPECS SHEETS FOR
 EACH OF THE PROPOSED TRANSPORTATION FEATURES (E.G.
 CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING, SIGNAL,
 ETC.)
 23) IDENTIFY AND DESIGNATE AN EASILY ACCESSIBLE
 MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20 FEET) AND
 PROVIDE BASIC ELECTRIFICATION READINESS WITH THE
 FOLLOWING SPECS: A CONDUIT (2-INCH SCHEDULE 40 PVC) TO
 THE POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V /
 10,000W CIRCUIT)
 24) PROVIDE A PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES
 25) ARE THERE ANY GATES PROPOSED? IF SO, CLEARLY
 SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE FROM THE
 BACK OF THE SIDEWALK OR CURB
 26) IS VALET SERVICE PROPOSED? IF SO, PROVIDE A
 THOROUGH OPERATIONAL ANALYSIS AND/OR PARKING MANAGEMENT
 PLAN
 27) ARE THERE ANY BUS STOPS BEING IMPACTED?
 28) IS THE PROPOSED DEVELOPMENT IMPACTING ANY EXISTING
 OR PLANNED BICYCLE FACILITY?
 29) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE
 REFER TO CITY CODE 86-246 FOR DETAILS
  