| 2022-11-06 09:10:06 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -SHOW ALL EXISTING AND PROPOSED FIRE HYDRANTS AND FDC |
| | ON ENGINEERING PLAN. |
| | -UTILITY BILLING SYSTEM INDICATES THERE IS AN EXISTING |
| | 6 INCH FIRELINE. |
| | -RELOCATE PROPOSED DOMESTIC WATER METER AND BACKFLOW |
| | ASSEMBLY CLOSER TO THE PROPERTY CORNER TO THE SOUTHWEST |
| | SO THAT CRANE TRUCK CAN ACCESS IT BETTER FROM SIDEWALK |
| | AND CANAL DRIVEWAY. |
| | -SHOW CONTINUATION OF PRIVATE FORCE MAIN TO WHERE IT |
| | CONNECTS TO CITY SEWER INFRASTRUCTURE. |
| | -IS THE EXISTING 2 INCH FORCE MAIN SUFFICIENTLY SIZED? |
| | -ADD PIPE MATERIAL TYPE TO LABEL OF 2 INCH FORCE MAIN. |
| | -ADD SIZE TO LABEL OF SANITARY SEWER LATERAL. |
| | -ADD NOTE TO WATER PLAN THAT WATER METERS SIZED 3 INCH |
| | OR LARGER NEED BE INSTALLED ABOVE-GROUND. |
| | -WATER PLAN NOTE 10 NOTED NO GREASE TRAPS PROPOSED |
| | BECAUSE OF NO FOOD OR BEVERAGE SERVICE, BUT |
| | JUSTIFICATION STATEMENT TALKED ABOUT A CAF??. PLEASE |
| | ENSURE COMPLIANCE WITH ANY GREASE TRAPS NEEDED. |
| | -WATER PLAN SHOWS EXISTING WELL, BUT HISTORIC PICTURES |
| | SHOW PIPE RUNNING TO CANAL. PLEASE VERIFY IF IRRIGATION |
| | SYSTEM GETTING WATER FROM A WELL, CANAL WATER, OR BOTH. |
| | -SHOW AND LABEL FRANCHISE UTILITIES ON ENGINEERING |
| | PLANS. HISTORIC PICTURES SHOW AT LEAST CABLE LOCATE |
| | MARKER IN AREA. |
| | -LANDSCAPING PLANS SHOW TREES IN 10 FOOT UTILITY |
| | EASEMENT. THOSE MAY CONFLICT WITH EXISTING AND FUTURE |
| | UTILITIES. |
| | -ADD VISUAL SCALE MEASUREMENT ICON TO WATER PLAN BLOWUP |
| | DETAIL. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |