2022-11-06 09:10:06PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SHOW ALL EXISTING AND PROPOSED FIRE HYDRANTS AND FDC
 ON ENGINEERING PLAN.
 -UTILITY BILLING SYSTEM INDICATES THERE IS AN EXISTING
 6 INCH FIRELINE.
 -RELOCATE PROPOSED DOMESTIC WATER METER AND BACKFLOW
 ASSEMBLY CLOSER TO THE PROPERTY CORNER TO THE SOUTHWEST
 SO THAT CRANE TRUCK CAN ACCESS IT BETTER FROM SIDEWALK
 AND CANAL DRIVEWAY.
 -SHOW CONTINUATION OF PRIVATE FORCE MAIN TO WHERE IT
 CONNECTS TO CITY SEWER INFRASTRUCTURE.
 -IS THE EXISTING 2 INCH FORCE MAIN SUFFICIENTLY SIZED?
 -ADD PIPE MATERIAL TYPE TO LABEL OF 2 INCH FORCE MAIN.
 -ADD SIZE TO LABEL OF SANITARY SEWER LATERAL.
 -ADD NOTE TO WATER PLAN THAT WATER METERS SIZED 3 INCH
 OR LARGER NEED BE INSTALLED ABOVE-GROUND.
 -WATER PLAN NOTE 10 NOTED NO GREASE TRAPS PROPOSED
 BECAUSE OF NO FOOD OR BEVERAGE SERVICE, BUT
 JUSTIFICATION STATEMENT TALKED ABOUT A CAF??. PLEASE
 ENSURE COMPLIANCE WITH ANY GREASE TRAPS NEEDED.
 -WATER PLAN SHOWS EXISTING WELL, BUT HISTORIC PICTURES
 SHOW PIPE RUNNING TO CANAL. PLEASE VERIFY IF IRRIGATION
 SYSTEM GETTING WATER FROM A WELL, CANAL WATER, OR BOTH.
 -SHOW AND LABEL FRANCHISE UTILITIES ON ENGINEERING
 PLANS. HISTORIC PICTURES SHOW AT LEAST CABLE LOCATE
 MARKER IN AREA.
 -LANDSCAPING PLANS SHOW TREES IN 10 FOOT UTILITY
 EASEMENT. THOSE MAY CONFLICT WITH EXISTING AND FUTURE
 UTILITIES.
 -ADD VISUAL SCALE MEASUREMENT ICON TO WATER PLAN BLOWUP
 DETAIL.