2022-11-06 08:08:22PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ON ENGINEERING PLANS, SHOW ALL EXISTING AND PROPOSED
 METERED WATER SERVICES, SANITARY SEWER LATERALS, SEWER
 CLEANOUTS, SANITARY SEWER MAINS, BACKFLOW ASSEMBLIES,
 AND WATER MAINS ON OR NEAR THE PROPERTY.
 -WILL THE SEPARATE EXISTING 560 S.F. SOUTHWEST BUILDING
 ALSO BE PART OF THE RESTAURANT WHERE FOOD IS PREPARED
 AND CUSTOMERS CAN DINE? IF NOT, WHAT WILL IT BE USED
 FOR?
 -SHOW ANY EXISTING OR PROPOSED GREASE TRAPS THAT ARE
 LOCATED OUTSIDE OF BUILDING.
 -HISTORIC PICTURES SHOW NO PARKING SIGNS AT DIXIE
 SIDEWALK.
 -HISTORIC PICTURES SHOW LIGHT POLE, UTILITY BOXES, AND
 VALVE BOX NEAR SOUTH DRIVEWAY. SHOW AND LABEL ON PLANS.
 -ADD WATER AND SEWER DEMAND CALCULATIONS TO ENGINEERING
 PLAN.
 -WILL ANY OF THE BUILDINGS HAVE FIRE SPRINKLERS?
 RESPECTFULLY,