| Plan Review Notes For Project Z22100018 |
| Project Number |
Z22100018 |
|
| Review Stop |
PU |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-24 15:21:04 | -COMMENT REGARDING EXISTING MANHOLES NEEDING REHABBING | | | NOT FULLY SATISFIED. PLEASE REVIEW PROPOSED PLANS AND | | | REVISE | | | -COMMENT REGARDING ONLY 8" LATERALS BEING ALLOWED | | | CONNECTION TO EXISTING MANHOLES NOT SATISFIED | | | -CLEANOUT ON PROPOSED SANITARY LATERAL IS 4" ON A 6" | | | LATERAL. | | | -CALL OUTS ARE NOT CLEAR ON DETAIL ON SHEET 5-1 | | | -PROVIDE DEMAND CALCULATIONS FOR BOTH EXISTING AND | | | PROPOSED CONDITIONS | | | -DOUBLE VALVING FOR NEW WATER MAIN REQUIRED AS PART OF | | | TESTING/SAMPLING PER CITY STANDARD DETAIL P-6 | | | -PROPOSED PROFILES ARE NOT SHOWING ALL EXISTING | | | CONFLICTS | | | -DEMO PLANS INCORRECTLY LISTING EXISTING 8" GATE VALVE | | | AND WATER MAIN ON GRUBER PLACE AS CAST IRON |
| |