2023-04-24 15:21:04-COMMENT REGARDING EXISTING MANHOLES NEEDING REHABBING
 NOT FULLY SATISFIED. PLEASE REVIEW PROPOSED PLANS AND
 REVISE
 -COMMENT REGARDING ONLY 8" LATERALS BEING ALLOWED
 CONNECTION TO EXISTING MANHOLES NOT SATISFIED
 -CLEANOUT ON PROPOSED SANITARY LATERAL IS 4" ON A 6"
 LATERAL.
 -CALL OUTS ARE NOT CLEAR ON DETAIL ON SHEET 5-1
 -PROVIDE DEMAND CALCULATIONS FOR BOTH EXISTING AND
 PROPOSED CONDITIONS
 -DOUBLE VALVING FOR NEW WATER MAIN REQUIRED AS PART OF
 TESTING/SAMPLING PER CITY STANDARD DETAIL P-6
 -PROPOSED PROFILES ARE NOT SHOWING ALL EXISTING
 CONFLICTS
 -DEMO PLANS INCORRECTLY LISTING EXISTING 8" GATE VALVE
 AND WATER MAIN ON GRUBER PLACE AS CAST IRON