Plan Review Notes
Plan Review Notes For Project Z22100018
Project Number Z22100018
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-11-08 09:15:28PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ON CIVIL PLANS, LABEL EXISTING WATER MAINS WITH PIPE
 SIZE AND MATERIAL TYPE. INCLUDE THAT INFO ON DEMO PLAN
 SHEET.
 -DEMO PLAN SHOWS WATER LINE RUNNING WEST FROM PROPOSED
 ABANDONED WATER MAIN. CALLOUT WHAT IS HAPPENING TO THAT
 WATER LINE, AND VERIFY WILL NOT LEAVE ATHLETIC BUILDING
 OUT OF SERVICE.
 -UPON FURTHER REVIEW, APPLICANT MAY BE REQUIRED TO
 REMOVE EXISTING WATER SERVICES FURTHER BACK TO THE
 WATER MAIN THAN PROPOSED.
 -UPON FURTHER REVIEW, APPLICANT MAY BE REQUIRED TO
 REMOVE WATER MAINS RATHER THAN ABANDON THEM.
 -UPON FURTHER REVIEW, APPLICANT MAY BE REQUIRED TO
 REMOVE EXISTING SEWER LATERALS RATHER THAN ABANDOM
 THEM.
 -CLEARLY SHOW AND LABEL ALL EXISTING AND PROPOSED WATER
 MAIN VALVES.
 -FIRE HYDRANT APPEARS TO BE TOO CLOSE TO TREE. CHECK
 CLEARANCE REQUIREMENT ON FIRE HYDRANT STANDARD DETAIL.
 -FIRE HYDRANT TYPICALLY HAS 6 INCH PIPE.
 -ADD SIZE OF FIRELINE BACKFLOW ASSEMBLY TO LABEL.
 -ADD SIZE AND RP TYPE TO LABEL OF PROPOSED DOMESTIC
 BACKFLOW ASSEMBLY.
 -ADD SIZE TO LABELS OF PROPOSED WATER METERS. METERS 3
 INCHES OR LARGER SHOULD BE INSTALLED ABOVE-GROUND.
 -IF WATER METER WILL BE 3 INCH OR LARGER, ENSURE THAT
 THE FOOTPRINT SIZE IS MORE ACCURATELY DEPICTED ON CIVIL
 PLANS.
 -THERE SUCH NOT BE A 3 INCH WATER SERVICE. 2 INCH WATER
 METERS HAVE 2 INCH WATER SERVICE PIPE WHILE 3 AND 4
 INCH METERS HAVE 4 INCH WATER SERVICE PIPE. ALSO ADD
 PIPE MATERIAL TYPE TO LABEL.
 -UTILITY PLAN SHOWS EXISTING WATER SERVICE AND TAP IN
 CLOSE PROXIMITY TO PROPOSED DOMESTIC WATER SERVICE.
 PLEASE PROVIDE ADEQUATE CLEARANCE DISTANCE BETWEEN
 TAPS.
 -CIVIL PLANS DO NOT SHOW PAVEMENT RESTORATION
 BOUNDARIES ON OLIVE AVE FOR UTILITY WORK BEING DONE IN
 THE ROADWAY. REFERENCE STANDARD DETAIL GC8 NOTE 1.
 -ARE ANY METERED IRRIGATION WATER SERVICES NEEDED?
 -ON DEMO PLAN, SHOW AND LABEL EXISTING WATER PIPE AND
 TEE FOR FIRE HYDRANT THAT IS PROPOSED TO BE REMOVED.
 -IF THERE WILL BE AN OUTDOOR GREASE TRAP THEN SHOW AND
 LABEL ON PLANS.
 -SHOW AND LABEL THE RELOCATED POLES AND OVERHEAD
 UTILITIES. ALSO SHOW ANY TRANSFORMER PADS.
 RESPECTFULLY,