| Plan Review Notes For Project Z22090019 |
| Project Number |
Z22090019 |
|
| Review Stop |
PU-CS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-06 11:20:14 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -LABEL FIRELINE BACKFLOW ASSEMBLIES WITH SIZE AND TYPE. | | | -DID NOT SEE FDC. SHOW AND LABEL IF NEEDED OR REQUIRED. | | | -LABEL WATER METERS WITH SIZE. IF SIZE IS 3 INCH OR | | | LARGER, ADD ABOVE-GROUND TO LABEL. | | | -NEAR NORTHEAST AREA OF PROPERTY, A FIRELINE PIPE MAY | | | HAVE LOCATION CONFLICT WITH A STORMWATER STRUCTURE. | | | -AT CALLOUT FOR EXISTING FIRE HYDRANT, ADD FIRE HYDRANT | | | SYMBOL ON PLANS. | | | -ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET C2.2 | | | -LABEL DOMESTIC BACKFLOW ASSEMBLIES WITH SIZE AND TYPE. | | | -WILL IRRIGATION WATER RUN OFF THE DOMESTIC METERED | | | WATER SERVICES? | | | -SHOW UTILITIES FROM CIVIL PLANS ON LANDSCAPING PLANS | | | AND ENSURE PLANTS AND UTILITIES ARE SUFFICIENTLY | | | DISTANCED FROM EACH OTHER. | | | -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED | | | CHEMICALS OR AUXILIARY WATER SOURCES SUCH AS WELLS. | | | -IF THERE WILL BE ANY OUTSIDE TRANSFORMER PADS, SHOW | | | AND LABEL ON PLANS. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |