Plan Review Notes
Plan Review Notes For Project Z22090019
Project Number Z22090019
Review Stop PU-CS
Sequence Number 2
Notes
Date Text
2023-07-06 11:20:14PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -LABEL FIRELINE BACKFLOW ASSEMBLIES WITH SIZE AND TYPE.
 -DID NOT SEE FDC. SHOW AND LABEL IF NEEDED OR REQUIRED.
 -LABEL WATER METERS WITH SIZE. IF SIZE IS 3 INCH OR
 LARGER, ADD ABOVE-GROUND TO LABEL.
 -NEAR NORTHEAST AREA OF PROPERTY, A FIRELINE PIPE MAY
 HAVE LOCATION CONFLICT WITH A STORMWATER STRUCTURE.
 -AT CALLOUT FOR EXISTING FIRE HYDRANT, ADD FIRE HYDRANT
 SYMBOL ON PLANS.
 -ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET C2.2
 -LABEL DOMESTIC BACKFLOW ASSEMBLIES WITH SIZE AND TYPE.
 -WILL IRRIGATION WATER RUN OFF THE DOMESTIC METERED
 WATER SERVICES?
 -SHOW UTILITIES FROM CIVIL PLANS ON LANDSCAPING PLANS
 AND ENSURE PLANTS AND UTILITIES ARE SUFFICIENTLY
 DISTANCED FROM EACH OTHER.
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SOURCES SUCH AS WELLS.
 -IF THERE WILL BE ANY OUTSIDE TRANSFORMER PADS, SHOW
 AND LABEL ON PLANS.
 RESPECTFULLY,
 MARK HURLEY [email protected]