Plan Review Notes
Plan Review Notes For Project Z22090019
Project Number Z22090019
Review Stop PU
Sequence Number 2
Notes
Date Text
2023-07-13 12:48:22-DENOTE MATERIAL FOR ALL EXISTING UTILITIES
 -SHOW ALL EXISITING UTILITIES WITHIN PROJECT SCOPE
 -SHOW ALL LATERALS/SERVICES WITHIN PROJECT SCOPE
 -SHOW ALL VALVES AND APPURTENANCES FOR EXISTING AND
 PROPOSED UTILITIES LEGIBLY
 -LABEL ALL EXISTING DRY UTILTIES
 -FITTINGS NOT PERMITTED BETWEEN METER AND BACKFLOW PER
 STANDARD DETAILS
 -CALL OUT ALL MEANS OF CONNECTION
 -CALL OUT SIZE AND MATERIAL FOR ALL PROPOSED UTILTIES
 -VALVES SHOWN WITHOUT SERVICES
 -PROVIDE 5 FOOT RADIAL CLEARANCE FOR METER BOXES AND
 CLEANOUTS
 -LATERALS/SERVICES NOT TO BE USED REQUIRE REMOVAL UP TO
 THE MAIN
 -DENOTE CITY'S POINTS OF SERVICE
 -PROVIDE PROFILES FOR ALL CONNECTIONS FROM POINT OF
 CONNECTION TO THE POINT OF SERVICE
 -PROVIDE DEMAND CALCULATIONS IN ORDER TO ENSURE
 EXISTING PIPES CAN PROVIDE SUFFICIENT FLOW
 -DATUM CONVERSION MISSING
 SPECIFY DOWNSTREAM LIFTSTATION THAT SERVES THE PROJECT
 AREA
 -PROVIDE CROSSING INFORMATION FOR ALL UTILITIES
 -LATERALS LARGER THAN 6" WILL REQUIRE CONNECTION VIA
 MANHOLE, AS WELL AS A CLEANOUT OF CORRESPONDING SIZE AT
 R/W
 -SAMPLE POINTS REQUIRED
 -FDOH PERMITS REQUIRED
 -BLOW-UP DETAIL NEEDED FOR ALL CONNECTION