Plan Review Notes
Plan Review Notes For Project Z22090019
Project Number Z22090019
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-10-11 08:02:49PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
  
 -CONSIDER ADDING GATE VALVE AT SOUTH SIDE OF PLUMBING
 HELP WITH TROUBLESHOOTING LEAKS AND MAINTENANCE.
  
 -LARGE METERS AND FIRELINE BACKFLOWS NEED TO BE OUTSIDE
 OF FENCES, GATES, OR WALLS AND ACCESSIBLE FROM RIGHT OF
 WAY. TREES SHOULD NOT BLOCK TRUCK CRANES FROM ACCESSING
 LARGE METERS.
  
 -PLUMBING SHOWN GOING THROUGH POSSIBLE POOL.
  
 -ARE ANY FDC NEEDED OR REQUIRED? IF SO, SHOW AND LABEL
 ON PLANS.
  
 -LABEL ON PLANS WHAT IS HAPPENING TO DO NOT PARK SIGNS
 NEAR NORTHEAST AREA OF PROPERTY.
  
 -ADD WATER AND SEWER DEMAND CALCS ON WATER AND
 WASTEWATER PLAN.
  
 -LARGE DOMESTIC BACKFLOW AND FIRELINE BACKFLOW STANDARD
 DETAILS MISSING. PLEASE ADD TO ENGINEERING PLAN SET.
  
 -HAVE GATES ON SOUTH PROPERTY LINE OPEN INWARD INSTEAD
 OF OUTWARD INTO CITY PROPERTY.
  
 -SURVEY SHOWS WOOD POWER POLES ON PROPERTY AND HISTORIC
 PICTURES SHOW OVERHEAD UTILITIES. WHAT IS HAPPENING TO
 THEM? ALSO ARE THERE ANY EXISTING UTILITY EASEMENTS FOR
 THOSE?
  
 -SHOW REMOVAL OF EXISTING SEWER LATERALS AND CLEANOUTS
 NEAR NORTH PROPERTY LINE AND RIGHT OF WAY ON WASTEWATER
 PLAN.
  
 -LABEL ADJACENT PROPERTY ADDRESSES TO THE SOUTH, EAST,
 AND WEST.
  
 -BACKFLOW ASSEMBLIES MAY NOT BE LOCATED IN SIDEWALKS
 BLOCKING PEDESTRIAN TRAFFIC.
  
 -LANDSCAPING PLAN DOES NOT SHOW PLANTS AND UTILITIES
 APPROPRIATELY DISTANCED FROM EACH OTHER.
  
 RESPECTFULLY,
  
 MARK HURLEY [email protected]
  