2023-07-25 13:09:00PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -RESPONSE LETTER SAID WATER AND SEWER DEMAND
 CALCULATIONS WERE ADDED TO SHEET C1.2, BUT CANNOT FIND
 THEM. PLEASE ADD.
 -RESPONSE LETTER SAID FDC IS AT SOUTHEAST BUILDING
 CORNER ON SHEET C1.2, BUT CANNOT FIND IT. PLEASE SHOW
 AND LABEL.
 -LANDSCAPE PLANS DO NOT SHOW UPDATED UTILITIES FROM
 ENGINEERING PLANS. PLEASE UPDATE LANDSCAPING PLANS TO
 SHOW PROPOSED UTILITIES.
 -PROPOSED 8 INCH FIRELINE WATER SERVICE WOULD NEED 8
 INCH DETECTOR FIRELINE BACKFLOW ASSEMBLY. SHOW AND
 LABEL IT NEAR THE NORTHEAST AREA OF PROPERTY.
 -ENGINEERING PLANS SHOW TWO SETS OF WATER METERS. LOOKS
 LIKE REVISED SYMBOLS WERE ADDED, BUT THE OLD SYMBOLS
 WERE NOT REMOVED AND THE CALLOUT LABELS NOT
 TRANSFERRED. PLEASE UPDATE ENGINEERING PLANS.
 -CONTAINMENT BACKFLOW ASSEMBLY LOCATIONS ARE NOT
 ACCEPTABLE NEAR THE WESTERN PROPERTY LINE. NEEDS TO BE
 NEAR THE EASTERN PROPERTY LINE. WHEN DETERMINING
 BACKFLOW LOCATIONS IT MAY HELP TO ALSO CONSIDER THE
 LANDSCAPING PLAN LAYOUT.
 -PE PIPE MATERIAL IS NOT ACCEPTABLE BETWEEN WATER METER
 AND DOMESTIC BACKFLOW ASSEMBLY.
 -LABEL WATER MAIN WITH PIPE SIZE AND MATERIAL TYPE.
 -UPDATE E22030048 WITH ANY CHANGES APPROVED THROUGH
 THIS PPRC PROJECT.